Investigation of Cascaded Commutation Failures in Multiple LCC-HVdc Inverters Caused by Rectifier Side AC Grid Faults

被引:0
|
作者
Xiao, Hao [1 ]
Acosta, Jhair S. [1 ]
Gole, Aniruddha M. [1 ]
Duan, Xianzhong [2 ]
Zhang, Yi [3 ]
机构
[1] Univ Manitoba, Dept Elect & Comp Engn, Winnipeg, MB R3T 2N2, Canada
[2] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, Wuhan 430074, Hubei, Peoples R China
[3] RTDS Technol Inc, Winnipeg, MB R3T 2E1, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Cascaded commutation failure; commutation failure immunity index; electromagnetic transient simulation; multi-infeed LCC-HVdc system; voltage distortion; SYSTEM; PREVENTION; VOLTAGE;
D O I
10.1109/TPWRD.2024.3419100
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In earlier work, cascaded commutation failure (CF) in multiple LCC-HVdc inverters of the multi-infeed system has been attributed to inverter side ac grid faults. However, this paper discusses a phenomenon where the cascaded CF is caused by rectifier side ac faults. The risk of this phenomenon is evaluated considering various fault inception instants, types, durations, and severities by electromagnetic transient simulations. The underlying mechanism of the phenomenon is identified by calculating the area under the commutating voltage curve. It is found that the commutating voltage waveform distortion arising from asymmetrical operation of the primary inverter after the fault clearance causes the initial CF. This CF subsequently introduces significant low-order harmonics into common inverter side ac grid, which propagate to the remote inverter ac bus and consequently induce the cascaded CF. It is also shown that if the tie-line impedance between inverter ac buses limits the propagation of low-order harmonics, the cascaded CF can be avoided. The dependency of the phenomenon on ac grid parameters is further quantified using the CF immunity index (CFII). It is inferred that the phenomenon is alleviated with the increased rectifier and inverter side ac grid strength as well as tie-line impedance magnitude at fundamental frequency.
引用
收藏
页码:2446 / 2456
页数:11
相关论文
共 21 条
  • [21] Research on Mechanism and Control Strategy of Continuous Commutation Failures in HVDC System Caused by Asymmetrical Fault in Inverter-Side AC System
    Zeng L.
    Li Y.
    Zhang Y.
    Sun G.
    Song J.
    Yang Z.
    Zhao X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2019, 39 (11): : 3159 - 3167