Power quality improvement of three-phase electrical systems using active-passive hybrid harmonic filter

被引:6
作者
Nor, Khairul Anuar Mohd [1 ,2 ]
Abdullah, Noramalina [1 ]
机构
[1] Univ Sains Malaysia, Sch Elect & Elect Engn, Pulau 10050, Pinang, Malaysia
[2] Univ Malaysia Perlis, Fac Elect Engn & Technol, Pauh Putra Campus, Arau 02600, Perlis, Malaysia
关键词
Active filter; Harmonic distortion; Hybrid filter; Passive filter; Three phase system;
D O I
10.1016/j.rineng.2024.102242
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
An overreliance on nonlinear load can result in electric current harmonics, which will ultimately result in a decrease in the quality of the electrical power. If a malfunction arises as a consequence of the internal integration of a power system in any of the internal networks, it will have an adverse effect on the overall operation of the power system. Because of this issue, there is a requirement for harmonic filters, which can minimize the levels of harmonics by referencing the IEEE-519 standards for enhancing power quality. This research offers an activepassive hybrid harmonic power filter to eliminate harmonic pollution in three-phase electrical systems. A MATLAB simulation and laboratory experiment proceeded for 240 Vac with nonlinear loads that represent by uncontrolled rectifier and series RLC load, and selected results were presented to verify the performance of the active-passive harmonic filter component. Upon completion of this research, an analysis of the conditions of a three-phase electrical system will be possible under four distinct circumstances: in the absence of a filter, with an active filter, with a passive filter, and with a hybrid filter. Furthermore, this model performs a comparative analysis of the percentage reduction in THD value achieved by the filter compared to the previous researcher. The result analysis reveals the proposed filter's good performance in eliminating harmonic pollution to 58.63 %, thereby significantly improving power quality. The findings presented in this study contribute to the ongoing efforts to ensure the reliable and efficient operation of modern power systems.
引用
收藏
页数:13
相关论文
共 29 条
  • [1] Performance Analysis of ANN Based three-phase four-wire Shunt Active Power Filter for Harmonic Mitigation under Distorted Supply Voltage Conditions
    Agrawal, Seema
    Palwalia, D. K.
    Kumar, Mahendra
    [J]. IETE JOURNAL OF RESEARCH, 2019, 68 (01) : 566 - 574
  • [2] [Anonymous], 2018, IEEE Std 3002.8-2018, P1, DOI DOI 10.1109/IEEESTD.2018.8479357
  • [3] Design of the hybrid harmonic filter to improve power quality of the grid connected hybrid renewable energy system
    Assi, Amirhossein
    Tafreshi, Seyed Masoud Moghaddas
    [J]. 2019 IRANIAN CONFERENCE ON RENEWABLE ENERGY & DISTRIBUTED GENERATION (ICREDG), 2019,
  • [4] Aswal Jyoti, 2018, 2018 2nd International Conference on Trends in Electronics and Informatics (ICOEI). Proceedings, P743, DOI 10.1109/ICOEI.2018.8553776
  • [5] Aswal J, 2018, PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON INVENTIVE SYSTEMS AND CONTROL (ICISC 2018), P668, DOI 10.1109/ICISC.2018.8398882
  • [6] Maciel LFA, 2018, IEEE INT AUT MEET
  • [7] Ayoub M.M., 2021, 2021 12 INT REN EN C, P1, DOI [10.1109/IREC52758.2021.9624858, DOI 10.1109/IREC52758.2021.9624858]
  • [8] Investigation on the Work Efficiency of the LC Passive Harmonic Filter Chosen Topologies
    Azebaze Mboving, Chamberlin Stephane
    [J]. ELECTRONICS, 2021, 10 (08)
  • [9] Boonseng C., 2019, INT C ELECTR MACH SY, P3171, DOI DOI 10.1109/icems.2019.8922558
  • [10] Cazacu E., 2023, 2023 10 INT C MOD PO, P1, DOI [10.1109/MPS58874.2023.10187576, DOI 10.1109/MPS58874.2023.10187576]