Heat transfer process and anti-frost performance of finned evaporator with air-water dual heat source for building heat supply

被引:2
作者
Li, Jinhua [1 ]
Long, Jibo [1 ]
Tan, Xin [1 ]
Zhang, Ruichao [2 ]
机构
[1] Xiangtan Univ, Coll Civil Engn, Xiangtan 411105, Hunan, Peoples R China
[2] Xian Univ Architecture & Technol, Sch Bldg Serv Sci & Engn, Xian, Peoples R China
关键词
Air source heat pump; dual heat source evaporator; heat exchange; COP; frosting; DEFROSTING METHOD; PREDICTION; EXCHANGER; PUMPS;
D O I
10.1080/17512549.2024.2365944
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this research, a dual heat source heat pump evaporator (AWSHP) with low-temperature hot water and air energy as the heat source is presented for the frosting problem of an air-source heat pump (ASHP) in low-temperature operating conditions. The critical frost region of the AWSHP system was also mapped using air temperature and water spray temperature as variables. The heat transfer characteristics as well as the anti-frost performance of AWSHP under different operating conditions were analyzed through experiments and simulations. According to the study's findings, the AWSHP system's refrigerant evaporation temperature was higher at the same ambient temperature than that of the ASHP. With AWSHP spray water volume of 8L/min and heat pump condenser circulating water volume of 15L/min, the average refrigerant heat exchanger and COP of AWSHP increased by 14.8% and 11.1%, respectively, compared with the ASHP system. At the same time, the AWSHP anti-frost operation strategy is proposed for low-temperature operating conditions. When the water spray volume was adjusted to 0.25 and 1.75 m(3)/h, respectively, under varying hourly meteorological conditions, the frost-free operation time was 61.21% and 89.24%, respectively. This was an improvement of 18.17% and 46.20%, respectively, compared to the ASHP.
引用
收藏
页码:426 / 452
页数:27
相关论文
共 41 条
[1]   A review of desiccant evaporative cooling systems in hot and humid climates [J].
Abd Manaf, Ismanizam ;
Durrani, Faisal ;
Eftekhari, Mahroo .
ADVANCES IN BUILDING ENERGY RESEARCH, 2021, 15 (01) :1-42
[2]   Electric defrosting analysis of a finned-tube evaporator coil using the enthalpy method [J].
Alebrahim, AM ;
Sherif, SA .
PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART C-JOURNAL OF MECHANICAL ENGINEERING SCIENCE, 2002, 216 (06) :655-673
[3]   CFD modeling of multiphase flows with detailed microkinetic description of the surface reactivity [J].
Bracconi, Mauro .
CHEMICAL ENGINEERING RESEARCH & DESIGN, 2022, 179 :564-579
[4]  
Chu B., 2019, LOW TEMP SUPERCOND, V47, P363, DOI [https://doi.org/10.16711/j.1001-7100.2019.05.010, DOI 10.16711/J.1001-7100.2019.05.010]
[5]   Experimental study of frost accumulation on fan-supplied tube-fin evaporators [J].
da Silva, Diogo L. ;
Hermes, Christian J. L. ;
Melo, Claudio .
APPLIED THERMAL ENGINEERING, 2011, 31 (6-7) :1013-1020
[6]   Life cycle energy, emissions and cost evaluation of CO2 air source heat pump system to replace traditional heating methods for residential heating in China: System configurations [J].
Dai, Baomin ;
Qi, Haifeng ;
Dou, Wanbin ;
Liu, Shengchun ;
Zhong, Dan ;
Yang, Haining ;
Nian, Victor ;
Hao, Ying .
ENERGY CONVERSION AND MANAGEMENT, 2020, 218
[7]  
Gao Q., 2011, EXPT STUDY FROST FRE
[8]   Annual performance analysis of solar-assisted raw-water source heat pumps at low water temperatures [J].
Han, Changho ;
Kim, Jinyoung ;
Cho, Wonhee ;
Shin, Hyun Ho ;
Lee, Hoseong ;
Kim, Yongchan .
ENERGY, 2024, 291
[9]   An experimental study on the operating performance of a novel reverse-cycle hot gas defrosting method for air source heat pumps [J].
Hu Wenju ;
Jiang Yiqiang ;
Qu Minglu ;
Ni Long ;
Yao Yang ;
Deng Shiming .
APPLIED THERMAL ENGINEERING, 2011, 31 (2-3) :363-369
[10]   Effect of fin types of outdoor fan-supplied finned-tube heat exchanger on periodic frosting and defrosting performance of a residential air-source heat pump [J].
Huang, Dong ;
Zhao, Ri-Jing ;
Liu, Yun ;
Yi, De-Bo .
APPLIED THERMAL ENGINEERING, 2014, 69 (1-2) :251-260