A single terminal fault location method for single phase fault of cable based on parameter identification of metal sheath model

被引:0
|
作者
Zhao T. [1 ]
Wang X. [1 ]
Yu Y. [1 ]
机构
[1] Qinhuangdao Power Supply Company, State Grid Jibei Electric Power Co., Ltd., Qinhuangdao
基金
中国国家自然科学基金;
关键词
Distribution network; Fault location; Least-square algorithm; Parameter identification; Single phase fault of cable;
D O I
10.19783/j.cnki.pspc.181575
中图分类号
学科分类号
摘要
Most of the cable faults are related to metal sheath, only considering the structural parameters of the guide core electrical model cannot realize the fault location of the protective layer. In order to solve the problem of distribution network single-phase cable fault location difficulties, a single terminal fault location method for cable single phase fault based on metal sheath model parameter identification is proposed. This paper first takes the single-phase distribution network fault zero mold equivalent network as the identification model, and fault distance, fault resistance, and capacitance to ground as the unknown parameters of the model, then uses the transient information cable after the single-phase grounding fault cable core and sheath and combines the fault state network and zero mold equivalent model to establish the time-domain ranging equation as a parameter the identification of the objective function, finally applies the least-square algorithm to solve the optimal parameters, obtaining the fault distance. ATP-EMTP simulation results verify the effectiveness of the proposed method, and the ranging accuracy is high. © 2019, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:83 / 91
页数:8
相关论文
共 21 条
  • [1] Du Y., Wang X.H., Yuan Z.H., Induced voltage sand power losses in single-conductor armored cables, IEEE Transactions on Industrial Applications, 45, 6, pp. 2145-2151, (2009)
  • [2] Shu H., Tian X., Dong J., Et al., A single terminal cable fault location method based on fault characteristic frequency band and TT transform, Proceedings of the CSEE, 31, 22, pp. 103-112, (2013)
  • [3] Liang R., Jin Z., Wang C., Et al., Research of fault location in distribution networks based on integration of travelling wave time and frequency analysis, Proceedings of the CSEE, 33, 28, pp. 130-136, (2013)
  • [4] Shu H., Wu Q., Zhang G., Et al., Single terminal traveling wave fault location method based on ANN, Proceedings of the CSEE, 31, 4, pp. 85-92, (2011)
  • [5] Fan C., Jiang J., Guo Y., Et al., Development and application of traveling wave fault location technology for transmission lines, Proceedings of the CSU-EPSA, 29, 4, pp. 129-134, (2017)
  • [6] Xue Y., Li L., Yu E., Et al., A sectionalized compensation based two-terminal traveling wave fault location algorithm for hybrid transmission line composed of power cable and overhead line, Power System Technology, 38, 7, pp. 1953-1958, (2014)
  • [7] Huang R., Li X., Zhang H., Et al., Research on combined traveling wave fault location method of overhead line-cable hybrid line and influencing factors, Power System Protection and Control, 46, 5, pp. 73-81, (2018)
  • [8] Yang J., Tang Z., Design of online traveling wave based fault location algorithm for HV power cable, Power System Protection and Control, 44, 14, pp. 48-54, (2016)
  • [9] Yan H., Gao Y., Wang J., Et al., Research on key problems of traveling wave location of double-circuit lines on the same tower, Power System Protection and Control, 46, 4, pp. 120-128, (2018)
  • [10] Dong X., Lei A., Tang L., Comparative study of traveling wave differential protection and current differential protection for power lines, Power System Protection and Control, 46, 1, pp. 1-8, (2018)