High Robustness Grid Current Feedback Active Damping Strategy for LCL-type Grid-connected Inverter in Weak Grid

被引:0
|
作者
Dong G. [1 ]
Xu Z. [2 ]
Sun P. [2 ]
Li Q. [2 ]
Chen Y. [1 ]
机构
[1] State Grid Chongqing Electric Power Research Institute, Yubei District, Chongqing
[2] State Key Laboratory of Power Transmission Equipment Technology (Chongqing University, Shapingba District, Chongqing
来源
Dianwang Jishu/Power System Technology | 2024年 / 48卷 / 04期
关键词
active damping; grid current feedback; LCL-type grid-connected inverter; robustness;
D O I
10.13335/j.1000-3673.pst.2023.0428
中图分类号
学科分类号
摘要
The grid-current-feedback-active-damping control strategy (GCFAD) has the function to effectively suppress the resonance peak of the LCL-type grid-connected inverter without requiring additional sensors. The GCFAD strategy is often used together with the grid voltage feedforward strategy to improve the quality of the grid current in a weak and disturbing grid. However, it is found that the positive resistance characteristics of the virtual impedance in the middle and low frequency bands under the traditional GCFAD strategy may cause a phase lag of the output impedance in the middle band, which reduces the robustness of the system when the grid voltage feedforward strategy is involved. In order to solve this problem, this paper proposes a high robustness grid-current-feedback- active-damping strategy (HR-GCFAD), which makes the virtual impedance exhibit positive resistance characteristics at high frequencies to suppress the LCL resonance peak and strengthen the stability of the system. It exhibits negative resistance characteristics in the middle and low frequency bands, which improves the robustness of the grid-connected inverter in a weak grid. Theoretical analysis and experimental results fully verify the effectiveness of the proposed strategy. © 2024 Power System Technology Press. All rights reserved.
引用
收藏
页码:1672 / 1680
页数:8
相关论文
共 20 条
  • [1] YAN Peilei, GE Xinglai, WANG Huimin, PLL parameter optimization design for renewable energy grid-connected inverters in weak grid[J], Power System Technology, 46, 6, pp. 2210-2221, (2022)
  • [2] JIANG Yuxia, TIAN Yanjun, LI Yonggang, Analysis of the influence of active power load fluctuation on the stability of distributed generation grid-connected inverter and improved control strategy[J], Power System Technology, 44, 2, pp. 646-654, (2020)
  • [3] Guoqiao SHEN, Xuancai ZHU, ZHANG Jun, A new feedback method for PR current control of LCL-filter-based grid-connected inverter[J], IEEE Transactions on Industrial Electronics, 57, 6, pp. 2033-2041, (2010)
  • [4] Wenli YAO, YANG Yongheng, ZHANG Xiaobin, Design and analysis of robust active damping for LCL filters using digital notch filters[J], IEEE Transactions on Power Electronics, 32, 3, pp. 2360-2375, (2017)
  • [5] ZHU Kunlong, SUN Pengjun, WANG Lin, High robustness weighted average current control for LCL-type grid-connected inverter in a weak grid[J], Proceedings of the CSEE, 40, 11, pp. 3592-3601, (2020)
  • [6] BAI Zhihong, XU Lin, Control strategies for the grid-connected inverter with LCL filter[J], Transactions of China Electrotechnical Society, 26, S1, pp. 118-124, (2011)
  • [7] Chenlei BAO, RUAN Xinbo, WANG Xuehua, Step-by-step controller design for LCL-type grid-connected inverter with capacitor–current-feedback active-damping[J], IEEE Transactions on Power Electronics, 29, 3, pp. 1239-1253, (2014)
  • [8] WANG Xuehua, Chenlei BAO, RUAN Xinbo, Design considerations of digitally controlled LCL-filtered inverter with capacitor-current-feedback active damping[J], IEEE Journal of Emerging and Selected Topics in Power Electronics, 2, 4, pp. 972-984, (2014)
  • [9] DANNEHL J, FUCHS F W,, HANSEN S, Investigation of active damping approaches for PI-based current control of grid-connected pulse width modulation converters with LCL filters[J], IEEE Transactions on Industry Applications, 46, 4, pp. 1509-1517, (2010)
  • [10] Jinming XU, Shaojun XIE, Ting TANG, Active damping-based control for grid-connected LCL-filtered inverter with injected grid current feedback only[J], IEEE Transactions on Industrial Electronics, 61, 9, pp. 4746-4758, (2014)