Review of Screening Sulfur Hexafluoride Alternative Gases Based on Density Functional Theory

被引:0
作者
Li X. [1 ]
Chen L. [1 ]
Fu M. [2 ]
Zhuo R. [2 ]
Wang D. [2 ]
Luo Y. [2 ]
机构
[1] State Key Laboratory of Electrical Insulation and Power Equipment, Xi'an Jiaotong University, Xi'an
[2] Electric Power Research Institute, China Southern Power Grid, Guangzhou
来源
Gaodianya Jishu/High Voltage Engineering | 2019年 / 45卷 / 03期
基金
中国国家自然科学基金;
关键词
Density functional theory; Electric strength; Screen; Temperature of boiling; Total electron-impact ionization cross-sections;
D O I
10.13336/j.1003-6520.hve.20190226001
中图分类号
学科分类号
摘要
Studies about environment-friendly SF6 alternatives have been paid more attentions recently. In this paper, the related researches on the method of sulfur hexafluoride substitutes based on density functional theory (DFT) are introduced. The screening methods for predicting the electric strength and liquefaction temperature of unknown insulating gas are described in detail, and the selected functional and basic set for calculation are analyzed. The influences of them on the calculation results indicate that the deviation between the calculated value and the experimental value is small at the M06-2X/6-311+G (3df) level. The influences of the microscopic parameters of the gas molecules selected during the prediction on the prediction results are compared. The analysis shows that the surface electrostatic potential is closely related to the liquefaction temperature and electric strength. The effects of halogen substitutions on the electric strength and liquefaction temperature of gas molecules and their changing rules are proposed. That is, as the relative molecular mass of halogens increases, the electric strength and liquefaction temperature also increase accordingly. In addition, the collision cross section of electron impact ionization is an important parameter for the study of insulation properties after screening. We compare the values of the collision section under the DM formula and the modified DM formula based on the density functional theory. The results show that the modified DM formula improves the accuracy of the calculation results. Finally, the direction of future research and development is pointed out, and a comprehensive evaluation system for SF6 alternative gas should be established under consideration of gas insulation, arc extinguishing, and environmental protection. © 2019, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:673 / 680
页数:7
相关论文
共 34 条
[1]  
Hernandezavila J.L., Basurto E., De Urquijo J., Electron transport and swarm parameters in CO<sub>2</sub> and its mixtures with SF<sub>6</sub>, Journal of Physics D: Applied Physics, 35, 18, (2002)
[2]  
Ueta G., Wada J., Okabe S., Evaluation of breakdown characteristics of CO<sub>2</sub> gas for non-standard lightning impulse waveforms - breakdown characteristics under single-frequency oscillation waveforms of 5.3 MHz to 20.0 MHz, IEEE Transactions on Dielectrics & Electrical Insulation, 18, 1, pp. 617-626, (2011)
[3]  
Zhao H., Li X., Jia S., Et al., Study on electrical breakdown characteristics of 50% SF<sub>6</sub>-50% CF<sub>4</sub> mixed gas at 1 atmosphere, Proceeding of the CSEE, 33, 19, pp. 200-207, (2013)
[4]  
Kieffel Y., Biquez F., SF<sub>6</sub> alternative development for high voltage switchgears, Electrical Insulation Conference, pp. 379-383, (2015)
[5]  
Mantilla J., Claessens M., Kriegel M., Environmentally friendly perfluoroketones-based mixture as switching medium in high voltage circuit breakers, CIGRE, (2016)
[6]  
Pohlink K., Kieffel Y., Owens J., Et al., Characteristics of fluoronitrile/CO<sub>2</sub> mixture-an alternative to SF<sub>6</sub>, CIGRE, pp. D1-D204, (2016)
[7]  
Preve C., Maladen R., Piccoz D., Method for validation of new eco-friendly insulating gases for medium voltage equipment, IEEE International Conference on Dielectrics, pp. 235-240, (2016)
[8]  
Kieffel Y., Biquez F., SF<sub>6</sub> alternative development for high voltage switchgears, Electrical Insulation Conference, pp. 379-383, (2015)
[9]  
Li X., Deng Y., Jiang X., Et al., Insulation performance and application of enviroment-friendly gases mixtures of C<sub>4</sub>F<sub>7</sub>N and C<sub>5</sub>F<sub>10</sub>O with CO<sub>2</sub>, High Voltage Engineering, 43, 3, pp. 708-714, (2017)
[10]  
Zhou W., Zheng Y., Yang S., Et al., Research progress and trend of environmentally friendly insulating gas replacing SF<sub>6</sub>, High Voltage Apparatus, 58, 12, pp. 8-14, (2016)