Novel partial discharge location in cast resin transformer using UHF method with scanning x-ray irradiation

被引:0
作者
Fujimura T. [1 ]
Kozako M. [1 ]
Hikita M. [1 ]
Iida K. [2 ]
Umemura T. [2 ]
Nakamura Y. [3 ]
Nakamae T. [4 ]
Maeda T. [4 ]
Higashiyama M. [4 ]
机构
[1] Kyushu Institute of Technology, 1-1, Sensui-cho, Tobata-ku, Kitakyushu
[2] Mie University, 1577 Kurimamachiya-cho, Tsu
[3] Toshiba Infrastructure Systems & Solutions Corporation, 1, Toshiba-cho, Fuchu
[4] TOSHIBA Industrial Products and Systems Co., Ltd., 2121 Nao, Asahi-cho, Mie-gun, Mie
关键词
Cast resin transformer; Partial discharge; UHF method; X-ray irradiation;
D O I
10.1541/ieejfms.140.162
中图分类号
学科分类号
摘要
It is crucial to detect void and delamination which might exist in cast resin transformer, because these defects can reduce insulation performance of cast resin equipment. It is considered that detecting partial discharge (PD) is effective to diagnose equipment of power equipment. This paper presents novel PD location using X-ray irradiation and UHF method in actual 6.6 kV class cast resin transformer VT as well as sample simulating the defect. By scanning a copper plate installed in front of a X ray generator to limit the X-ray irradiation range, the defect position was successfully determined with 10 mm accuracy. it was also shown that PD source in a larger size 33 kV class VT can be located by the time of flight of the electromagnetic wave detection signal by UHF method. © 2020 Institute of Electrical Engineers of Japan. All rights reserved.
引用
收藏
页码:162 / 168
页数:6
相关论文
共 13 条
[1]  
Shibuya Y., Kozako M., Takada H., Hirose T., Higashiyama M., Nakamura S., Umemura T., Void formation and electrical breakdown in epoxy resin, IEEE Trans. Power Appar. & Syst., 96, 1, pp. 198-207, (1977)
[2]  
Hikita M., Kozako M., Takada H., Hirose T., Higashiyama M., Nakamura S., Umemura T., Partial discharge phenomena in artificial cavity in epoxy cast resin insulation system, IEEE International Symposium on Electrical Insulation, (2010)
[3]  
Higashiyama M., Akiyama K., Maeda T., Nakamura S., Umemura H., Hikita M., Lifetime evaluation of oil-immersed power capacitor using conversion factor between model sample and practical equipment, IEEJ Trans. PE, 131, 3, pp. 329-334, (2011)
[4]  
Higashiyama M., Suzuki H., Hirose T., Nakamura Y., Maeda T., Hayama T., Nakamura S., Umemura T., Kozako M., Hikita M., Insulation behavior of small-air-gap for the molded-insulation system, IEEJ Trans. PE, 131, 7, pp. 630-636, (2011)
[5]  
Higashiyama M., Hirose T., Nakamura Y., Maeda T., Nakamura S., Umemura T., Kozako M., Hikita M., Insulation behavior of small-air-gap for the molded-insulation system (2)-partial discharge behavior of MGM and MGI systems-, IEEJ Trans. PE, 133, 2, pp. 203-209, (2013)
[6]  
Takada H., Hayashi M., Kozako M., Hikita M., Nakamura S., Umemura T., Nakamura Y., Hirose T., Higashiyama M., Investigation of partial discharge phenomena in artificial cavity in epoxy cast resin insulation system, IEEJ Trans. FM, 131, 9, pp. 785-791, (2011)
[7]  
Higashiyama M., Takada H., Hayashi M., Kozako M., Hikita M., Nakamura S., Umemura T., Nakamura Y., Hirose T., Investigation of partial discharge characteristics induced by x-ray irradiation in artificial cavity in epoxy resin, IEEJ Trans. FM, 132, 4, pp. 284-290, (2012)
[8]  
Zhao X., Cheng Y., Meng Y., Wu K., Niu Y., The propagation characteristics of UHF partial discharge in power transformers with complex winding structure, Annual Report Conference on Electrical Insulation and Dielectric Phenomena, (2012)
[9]  
Maki J., Akinaga Y., Kozako M., Hikita M., Nakamura Y., Taniguchi K., Ikeda Y., Okamoto K., Novel partial discharge location algorithm for next generation power module using small loop sensors, International Conference on Integrated Power Electronics, pp. 186-191, (2018)
[10]  
Su C.-C., Tai C.-C., Chen C.-Y., Hsieh J.-C., Chen J.-F., Partial discharge detection using acoustic emission method for a waveguide functional high-voltage cast-resin dry-type transformer, International Conference on Condition Monitoring and Diagnosis, E2-06, (2008)