Conceptual design and preliminary experimental study on curved PV ventilated facade assisted heat pump system (CPVF-HP)

被引:12
作者
Cai, Jingyong [1 ,2 ]
Liang, Mengyao [1 ]
Fang, Jianxiao [1 ]
Shi, Zhengrong [1 ,2 ]
Xu, Lijie [3 ]
机构
[1] Shanghai Univ Elect Power, Coll Energy & Mech Engn, Shanghai 201306, Peoples R China
[2] Shanghai Noncarbon Energy Convers & Utilizat Inst, Shanghai 200240, Peoples R China
[3] Jimei Univ, Inst Marine Engn, Prov Key Lab Naval Architecture & Ocean Engn, Xiamen 361021, Peoples R China
基金
中国国家自然科学基金;
关键词
Curved photovoltaic; Ventilated facade; Heat pump; Experiment; Synergistic operation; BUILDINGS; PERFORMANCES; COLLECTOR; WALL;
D O I
10.1016/j.enconman.2024.118277
中图分类号
O414.1 [热力学];
学科分类号
摘要
Integrating photovoltaic PV with curved architecture boosts renewable energy use and reduces carbon emissions in building applications. This paper proposes a curved PV ventilated facade assisted heat pump system (CPVFHP), utilizing curved PV ventilation facade as carrier for the application of PV in curved buildings, and enhancing overall energy efficiency through synergistic operation with heat pumps. In the cooling mode, the system employs the heat pump evaporator to pre -cool the air entering the curved PV ventilated facade, thereby reducing the temperature of the PV cells and the air conditioning load of the building. In the heating mode, the CPVF-HP system preheats the air entering the heat pump evaporator using the curved PV ventilated facade, elevating the evaporation temperature of the heat pump. The experimental setup of CPVF-HP is established, and the dynamic performance of the CPVF under various ventilation conditions and its synergistic operational performance with the heat pump have been investigated. The results indicate that CPVF displays considerable difference in irradiance and temperature across its east - west orientation, especially noticeable during morning and afternoon hours, affecting the system ' s electrical performance. Notably, isotropic scattered radiation improves radiation uniformity and the electrical efficiency of CPVF. The system achieves a notable average electrical efficiency increase of 69.90% on cloudy days compared to sunny conditions. CPVF-HP system effectively manages temperatures by precooling or preheating the air, enhancing the electrical efficiency by 34.43% in cooling mode, and increasing COP by 5.23% in heating mode compared to an independent heat pump operation. The CPVF-HP system demonstrates a synergistic improvement in both thermal and electrical performance, offering an innovative approach to optimizing energy efficiency in curved PV integrated buildings.
引用
收藏
页数:21
相关论文
共 32 条
[1]   Energy Harvest Potential of Flexible Photovoltaics on Curved Surfaces [J].
Alpuerto, Lance ;
Balog, Robert S. .
2019 IEEE TEXAS POWER AND ENERGY CONFERENCE (TPEC), 2019,
[2]   Modeling and simulation of a photovoltaic/thermal air collector assisting a facade integrated small scale heat pump with radiant PCM panel [J].
Bigaila, E. ;
Athienitis, A. K. .
ENERGY AND BUILDINGS, 2017, 149 :298-309
[3]   Multi-objective optimization of a photovoltaic thermal curtain wall assisted dual-source heat pump system [J].
Chang, Shasha ;
Feng, Guohui ;
Zhang, Lei ;
Huang, Kailiang ;
Li, Ainong .
APPLIED THERMAL ENGINEERING, 2023, 222
[4]  
D.o.E.s.D.B.T.O. (BTO) N.R.E.L. (NREL), ABOUT US
[5]  
Duffie JA, 2013, SOLAR ENGINEERING OF THERMAL PROCESSES, 4TH EDITION, P1, DOI 10.1002/9781118671603
[6]   Analysis of the performances of a building-integrated PV/Thermal system [J].
Gagliano, Antonio ;
Tina, Giuseppe Marco ;
Aneli, Stefano ;
Chemisana, Daniel .
JOURNAL OF CLEANER PRODUCTION, 2021, 320 (320)
[7]   A photovoltaic forced ventilated facade (PV-FVF) as heat source for a heat pump: Assessing its energetical profit in nZEB buildings [J].
Garcia-Gafaro, C. ;
Escudero-Revilla, C. ;
Flores-Abascal, I ;
Hidalgo-Betanzos, J. M. ;
Erkoreka-Gonzalez, A. .
ENERGY AND BUILDINGS, 2022, 261
[8]   The role of residential rooftop photovoltaic in long-term energy and climate scenarios [J].
Gernaat, David E. H. J. ;
de Boer, Harmen-Sytze ;
Dammeier, Louise C. ;
van Vuuren, Detlef P. .
APPLIED ENERGY, 2020, 279
[9]   A comparative evaluation on the case for the implementation of building integrated photovoltaic/thermal (BIPV/T) air based systems on a typical mid-rise commercial building in Canadian cities [J].
Hasan, Javeriya ;
Fung, Alan S. ;
Horvat, Miljana .
JOURNAL OF BUILDING ENGINEERING, 2021, 44
[10]   Performance study of a dual-function roof solar collector for Chinese traditional buildings application [J].
Hu, Zhongting ;
Luo, Bingqing ;
He, Wei ;
Hu, Dengyun ;
Ji, Jie ;
Ma, Jinwei .
APPLIED THERMAL ENGINEERING, 2018, 128 :179-188