Modeling and Simulation of Dynamic Phasor Harmonic Analysis for Frequency-Dependent Transmission Line

被引:0
|
作者
Xie R. [1 ]
Zhang G. [1 ]
Gao K. [1 ]
Peng B. [1 ]
机构
[1] School of Electrical Engineering and Automation, Hefei University of Technology, Hefei
关键词
Dynamic phasor; Frequency-dependent transmission line; Harmonic analysis; Power quality; Vector fitting method;
D O I
10.19595/j.cnki.1000-6753.tces.201021
中图分类号
学科分类号
摘要
The windowed fast Fourier transform(WFFT) is widely used for harmonic analysis on rapidly changing time domain waveforms in power electronic distribution network, but WFFT is prone to errors so that the harmonic transient characteristics cannot be obtained accurately. In this paper, a dynamic phasor (DP) model of frequency-dependent transmission line is proposed for harmonic transient analysis in distribution network. The characteristic admittance and propagation coefficient are fitted in rational function by adopting vector fitting method, which exist in the model domain frequency-dependent transmission line model. The DP model of frequency-dependent transmission line is established based on state space equation, the DP model is also established for the thyristor controlled reactor (TCR) at receiving end of the transmission line, the harmonic dynamic coupling between TCR and power grid is described by the analytical formula with phasors of each order as state variables. The DP model of the simple test system is calculated based on Matlab, which can directly analyze harmonic transient characteristics forthe voltage of each node and currentin each branch in the system, and the instantaneous power quality parameters can also be obtained. The transient steady state results of the simulation system based on EMTP verify the effectiveness and accuracy of the model. © 2021, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:3200 / 3210
页数:10
相关论文
共 26 条
  • [1] Bollen M H J, Das R, Djokic S, Et al., Power quality concerns in implementing smart distribution-grid applications, IEEE Transactions on Smart Grid, 8, 1, pp. 1-8, (2016)
  • [2] Xiao Xiangning, Liao Kunyu, Tang Songhao, Et al., Development of power-electronized distribution grids and the new supraharmonics issues, Transactions of China Electrotechnical Society, 33, 4, pp. 707-720, (2018)
  • [3] Tao Shun, Luo Chao, Xiao Xiangning, Et al., A modified current physical components theory and its application in power quality assessment, Transactions of China Electrotechnical Society, 34, 9, pp. 1960-1970, (2019)
  • [4] Yan Jing, Shao Zhenguo, Summary of harmonic monitoring and evaluation, Electrical engineering, 21, 7, pp. 1-7, (2020)
  • [5] Xie Ning, Luo An, Chen Yandong, Et al., Dynamic modeling and characteristic analysis on harmonics of photovoltaic power stations, Proceedings of the CSEE, 33, 36, pp. 10-17, (2013)
  • [6] Medina A, Segundo J, Ribeiro P, Et al., Harmonic analysis in frequency and time domain, IEEE Transactions on Power Delivery, 28, 3, pp. 1813-1821, (2013)
  • [7] Cheng Peifen, Li Chongtao, Fu Chuang, Et al., An analytic solution for simplified electromagnetic transient model of HVDC transmission system based on state space method, Transactions of China Electrotechnical Society, 34, 6, pp. 1230-1239, (2019)
  • [8] Wang Baoshuai, Xiao Xia, A high accuracy Multi-spectrum-line interpolation algorithm for harmonic analysis, Transactions of China Electrotechnical Society, 33, 3, pp. 553-562, (2018)
  • [9] Li Jianmin, Lin Haijun, Liang Chengbin, Et al., Detection method of power quality disturbances based on double resolution s transform and learning vector quantization neural network, Transactions of China Electrotechnical Society, 34, 16, pp. 3453-3463, (2019)
  • [10] Gallo D, Langella R, Luiso M, Et al., A new test procedure to measure power electronic devices frequency coupling admittance, IEEE Transactions on Instrumentation & Measurement, 67, 10, pp. 2401-2409, (2018)