Analysis of the commutation failure process and a study on the influence of operation parameters on a UHVDC system

被引:0
|
作者
Han P. [1 ]
Tong Q. [1 ]
Yang W. [2 ]
Chen Z. [2 ]
Sun H. [1 ]
Zhang Y. [3 ]
机构
[1] Anhui Provincial Key Laboratory of Renewable Energy Utilization and Energy Saving (Hefei University of Technology), Hefei
[2] State Grid Anhui Electric Power Company Limited Research Institute, Hefei
[3] No. 38 Research Institute of CETC, Hefei
来源
Tong, Qingyang (tqyhfut0325@163.com) | 1600年 / Power System Protection and Control Press卷 / 49期
关键词
Commutation failure; Operation parameters; Process analysis; Sensitivity; UHVDC;
D O I
10.19783/j.cnki.pspc.201498
中图分类号
学科分类号
摘要
An AC system fault at the receiving end is the main cause of commutation failure in an Ultra High Voltage Direct Current (UHVDC) system. This can seriously affect the security of the power grid. To fully clarify the commutation process and control response of a valve group during commutation failure of a UHVDC system under an AC system fault, the actual extinction area and the minimum extinction area of the valve group are compared, and the main reason for commutation failure is analyzed through the electromagnetic transient simulation of the fault process. Sensitivity of operational parameters and commutation failure and the fault recovery process is studied. It is found that the parameters of a Voltage Dependent Current Order Limiter (VDCOL), proportional coefficient and integral coefficient of inverter control have obvious effects on commutation failure and the fault recovery process. These aspects can be the first choice for optimizing of the control system. This paper can provide a reference for commutation failure analysis and stable operation of a UHVDC converter station. © 2021 Power System Protection and Control Press.
引用
收藏
页码:25 / 34
页数:9
相关论文
共 24 条
  • [1] WANG Qi, ZHANG Chaoming, WU Xingquan, Et al., Commutation failure prediction method considering commutation voltage distortion and DC current variation, IEEE Access, 7, pp. 96531-96539, (2019)
  • [2] HAN Pingping, CHEN Lingqi, DING Ming, Et al., A kind of hybrid HVDC transmission system suitable for wind power connection, Acta Energiae Solaris Sinica, 40, 8, pp. 2162-2169, (2019)
  • [3] CHEN Jiahao, WANG Qi, ZHU Xinyao, Et al., Risk assessment of commutation failure for HVDC transmission due to harmonic voltage, High Voltage Apparatus, 56, 5, pp. 196-202, (2020)
  • [4] XUE Ying, ZHANG Xiaoping, YANG Conghuan, Commutation failure elimination of LCC HVDC systems using thyristor-based controllable capacitors, IEEE Transactions on Power Delivery, 33, 3, pp. 1448-1458, (2018)
  • [5] CHENG Yan, ZHANG Jian, GUAN Ti, Et al., Coordinated control strategy of voltage and frequency support at receiving end of HVDC system under commutation failure, High Voltage Apparatus, 56, 4, pp. 241-245, (2020)
  • [6] WANG Shaohui, TANG Fei, XIANG Nong, Commutation failure simulation analysis of East China power grid multiple HVDC lines, Power System Protection and Control, 45, 12, pp. 16-21, (2017)
  • [7] SHAO Yao, TANG Yong, Fast evaluation of commutation failure risk in multi-Infeed HVDC systems, IEEE Transactions on Power Systems, 33, 1, pp. 646-653, (2018)
  • [8] WANG Sichao, WEN Jun, HE Dongshan, Et al., Commutation failure control and recovery strategy of UHVDC with hierarchical connection mode, Power System Protection and Control, 48, 2, pp. 172-179, (2020)
  • [9] THIO C V, DAVIES J B, KENT K L., Commutation failures in HVDC transmission system, IEEE Transactions on Power Delivery, 11, 2, pp. 946-957, (1996)
  • [10] MIRSAEIDI S, DONG Xinzhou, TZELEPIS D, Et al., A predictive control strategy for mitigation of commutation failure in LCC-based HVDC systems, IEEE Transactions on Power Electronics, 34, 1, pp. 160-172, (2019)