Wavelet transform-based ground fault detection for LVDC microgrid

被引:0
作者
Lee K.-M. [1 ,2 ]
Park C.-W. [1 ,2 ]
机构
[1] Dept. of Electrical Engineering, Gangneung-Wonju National University
[2] Dept. of Electrical Engineering, Gangneung-Wonju National University
关键词
Ground fault detection; LVDC microgrid; PSCAD; Signal injection method; Ungrounded system; Wavelet transform;
D O I
10.5370/KIEE.2021.70.9.1289
中图分类号
学科分类号
摘要
LVDC Microgrid is a small-scale power grid that can increase the stability and efficiency of power supply in a small area, enabling independent operation and increasing the acceptability of DERs (Distributed Energy Resources). However, this is an ungrounded IT (Isolated Terre) grounding system, and even when a ground fault occurs, there is no fault current path and no significant difference compared to the steady state current, so fault detection is very difficult. WT (Wavelet Transform), an easy tool for transient analysis and signal identification, is to be applied to the detection of ground faults in LVDC Microgrid. In this paper, we propose a Wavelet transform-based ground fault detection method for an ungrounded LVDC Microgrid. By changing the level and order of various MW (Mother Wavelets) using the current collected in the existing pulse injection method, the optimal MW for ground fault detection method is derived. First, an ungrounded LVDC Microgrid is modeled using PSCAD s/w, and ground faults are simulated by varying the fault point and fault resistance. We implement the selected optimal Wavelet transform-based ground fault detection method using Matlab s/w. Finally, performance evaluation is performed through simulation using various collected signals. Copyright © The Korean Institute of Electrical Engineers.
引用
收藏
页码:1289 / 1294
页数:5
相关论文
共 19 条
[1]  
Seo Hae-Won, Han Young-Seong, Jeong Byeong-Hwan, Kim Hong-Joo, Cho Young-Pyo, Kim Ju-Yong, Status and Application of High Capacity Energy System for Verification of Power Distribution Network, KIEE Summer Conference, pp. 885-886, (2018)
[2]  
Cho Young-Pyo, Development of performance evaluation system for power conversion device for DC distribution link, KIEE Fall Conference, pp. 218-221, (2019)
[3]  
Chang S.Y., LVDC distribution technology trend, KIIEE Spring Conference, LVDC Workshop, pp. 151-164, (2018)
[4]  
Park C.W., Hong J.Y., Jin H.S., Lee K.M., Selection of Optimal Mother Wavelet for Ground Fault Detection of DC Distribution System, KIEE Summer Conference, pp. 1-2, (2019)
[5]  
Kim Jong-Woo, Development of End-User-Side LVDC Power Supplies and Core Devices for Interacting Distributed Power Sources, KETEP, proposal, pp. 1-326, (2019)
[6]  
Ham J.M., Lee K.M., Sung N.K., Hwang J.I., Cho N.H., Park C.W., CB Capacity Calculation for DC Grid, KIEE Summer Conference, pp. 1-2, (2021)
[7]  
Cho Young-Pyo, Kang Sae-Il, Kim Wonse, Kim Seung-Wan, CIRED Summer Conference, KIEE Summer Conference, Workshop, CIRED Korea Committee, pp. 1-126, (2021)
[8]  
Park C.W., Lee K.M., A Study on Fault Current Calculation of ±750[V] DC Distribution Grid, Trans. on KIEE, 67, 10, pp. 1286-1291, (2018)
[9]  
Ashrafian Abdolaziz, Mirsalim Mojtaba, Masoum Mohammad A. S., Application of a Recursive Phasor Estimation Method for Adaptive Fault Component Based Differential Protection of Power Transformers, IEEE Transactions on Industrial Informatics, 13, 3, pp. 1381-1392, (2017)
[10]  
Som Shreyasi, Samantaray Subhransu Ranjan, Efficient protection scheme for low-voltage DC micro-grid, IET Generation, Transmission & Distribution, 12, 13, pp. 3322-3329, (2018)