A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors

被引:4
作者
Wu, Jie [1 ,2 ]
Zhen, Wei [1 ,2 ]
Chang, Zhengwei [1 ,2 ]
Zhang, Man [3 ]
Peng, Yumin [3 ]
Liu, Ying [3 ]
Huang, Qi [3 ]
机构
[1] State Grid Sichuan Elect Power Co, Elect Power Res Inst, Chengdu 610041, Peoples R China
[2] Power Internet Things Key Lab Sichuan Prov, Chengdu 610041, Peoples R China
[3] Univ Elect Sci & Technol China, Sch Mech & Elect Engn, Chengdu 610059, Peoples R China
关键词
dry-type air-core shunt reactors; inter-turn short-circuit fault; equivalent resistance; high sensitivity;
D O I
10.3390/en17071709
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Dry-type air-core shunt reactors are integral components in power transmission and distribution networks, designed to control reactive power and enhance system stability. However, inter-turn short-circuit faults (ISCFs) are common occurrences in shunt reactors, which are caused by various factors, including manufacturing defects, insulation degradation, or operational stresses. At the early stage of the ISCFs, the current does not reach a sufficient level to activate the protective equipment. These faults may lead to serious consequences, such as overheating, insulation breakdown, and even catastrophic failures, posing risks to the entire power system. Therefore, developing an effective and reliable detection method for ISCFs at the early stage is paramount. In this paper, a new method named the fault detection factor (FDF) based on equivalent resistance is presented to detect the slight ISCFs in dry-type air-core shunt reactors considering insulation resistance. In addition, the effect of noise signal existence in the monitoring process is taken into account. A moving average filter is adopted to guarantee both the sensitivity and the reliability of the proposed method. Ultimately, the simulation results of the FDF under different conditions are presented, which show the effectiveness and potential of the proposed method in observing and monitoring slight ISCFs.
引用
收藏
页数:14
相关论文
共 30 条
[1]  
Chen J., 2018, P IEEE INT C PROPERT, DOI [10.1109/icpadm.2018.8401165, DOI 10.1109/ICPADM.2018.8401165]
[2]   A Novel Hybrid Differential Algorithm for Turn to Turn Fault Detection in Shunt Reactors [J].
Das, Sarasij ;
Sidhu, Tarlochan S. ;
Zadeh, Mohammad Reza Dadash ;
Zhang, Zhiying .
IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (06) :2537-2545
[3]  
Gao Z.W., 2017, J. Harbin Univ. Sci. Technol, V22, P67, DOI [10.15938/j.jhust.2017.02.013, DOI 10.15938/J.JHUST.2017.02.013]
[4]  
[郭哲 Guo Zhe], 2020, [电力系统自动化, Automation of Electric Power Systems], V44, P149
[5]  
He L., 2020, P 2020 CHINESE CONTR, DOI [10.1109/CCDC49329.2020.9164052, DOI 10.1109/CCDC49329.2020.9164052]
[6]  
He L., 2020, P 2020 CHINESE CONTR, DOI [10.1109/CCDC49329.2020.9164079, DOI 10.1109/CCDC49329.2020.9164079]
[7]   Robust Stator Winding Fault Detection in PMSMs With Respect to Current Controller Bandwidth [J].
Huang, Shaopo ;
Aggarwal, Anmol ;
Strangas, Elias G. ;
Li, Kui ;
Niu, Feng ;
Huang, Xiaoyan .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2021, 36 (05) :5032-5042
[8]  
Jiang J.Q., CSU-EPSA, DOI [10.19635/j.cnki.csu-epsa.001319, DOI 10.19635/J.CNKI.CSU-EPSA.001319]
[9]  
Li N., 2022, Electr. Eng, V15, P83, DOI [10.19768/j.cnki.dgjs.2022.15.021, DOI 10.19768/J.CNKI.DGJS.2022.15.021]
[10]  
Li Qi, 2019, 2019 IEEE 3rd Conference on Energy Internet and Energy System Integration (EI2), P2303, DOI 10.1109/EI247390.2019.9061955