VSC-HVDC Line Protection Principle Based on the Similarity of the Double-ended Initial Current Traveling Wave Time-frequency Matrices

被引:0
|
作者
Zhang Y. [1 ]
Wang C. [1 ]
Yu Y. [1 ]
Yang G. [1 ]
Cao H. [1 ]
机构
[1] State Key Laboratory for Security and Energy Saving (China Electric Power Research Institute), Haidian District, Beijing
关键词
double-ended protection; initial current traveling wave (IVTW); time-frequency matrix; voltage source converter-based high voltage DC (VSC-HVDC) grid;
D O I
10.13334/j.0258-8013.pcsee.221953
中图分类号
学科分类号
摘要
Aiming at the problems currently existing in line protection for voltage source converter-based high voltage DC (VSC-HVDC) grids, a double-ended protection principle based on similarity of time-frequency matrix of initial current traveling wave (ICTW) is proposed. First, the fault characteristics of the ICTWs on both sides of the line in the flexible DC grids under internal and external faults are analyzed. It is concluded that within a specific time window, the frequency-domain similarities of the double-ended ICTWs under internal faults are much higher than those under external faults. Then, the double-ended ICTWs are performed S-transform, and the time-frequency matrices are obtained. Then singular value decomposition (SVD) is performed on the matrices. Afterwards, the similarity calculation formula of the double-ended ICTWs is constructed based on the feature matrices, and the internal and external faults can be identified by the value of the similarity. In addition, lightning interference is identified according to the high and low frequency energy ratio of the ICTWs at both ends of the line. Finally, the simulation results under various fault conditions show that the protection scheme does not rely on line boundary elements; it can protect the full length of lines with different lengths; it has stronger robustness against transition resistance and noise. Besides, it satisfies the quick identification requirements of the main protection for VSC-HVDC grids. ©2024 Chin.Soc.for Elec.Eng.
引用
收藏
页码:2604 / 2615
页数:11
相关论文
共 31 条
  • [1] LI Botong, LV Mingrui, LI Bin, Research on an improved protection principle based on differential voltage traveling wave for VSC-HVDC transmission lines [J], IEEE Transactions on Power Delivery, 35, 5, pp. 2319-2328, (2020)
  • [2] LU Zongxiang, YE Yida, QIAO Ying, An adaptive frequency regulation method with grid-friendly restoration for VSC-HVDC integrated offshore wind farms[J], IEEE Transactions on Power Systems, 34, 5, pp. 3582-3593, (2019)
  • [3] ZHENG Huajun, ZHOU Luowei, SUN Pengju, Large-signal stability analysis for VSC-HVDC systems based on mixed potential theory[J], IEEE Transactions on Power Delivery, 35, 4, pp. 1939-1948, (2020)
  • [4] LETERME W, BEERTEN J, VAN HERTEM D., Nonunit protection of HVDC grids with inductive DC cable termination[J], IEEE Transactions on Power Delivery, 31, 2, pp. 820-828, (2016)
  • [5] SNEATH J, RAJAPAKSE A D., Fault detection and interruption in an earthed HVDC grid using ROCOV and hybrid DC breakers[J], IEEE Transactions on Power Delivery, 31, 3, pp. 973-981, (2016)
  • [6] ZHANG Chenhao, LI Yang, SONG Guobing, Fast and sensitive nonunit protection method for HVDC grids using levenberg-marquardt algorithm[J], IEEE Transactions on Industrial Electronics, 69, 9, pp. 9064-9074, (2022)
  • [7] HUANG Qiang, ZOU Guibin, ZHANG Shuo, A pilot protection scheme of DC lines for multi-terminal HVDC grid[J], IEEE Transactions on Power Delivery, 34, 5, pp. 1957-1966, (2019)
  • [8] LI Chengyu, GOLE A M, ZHAO Chengyong, A fast DC fault detection method using DC reactor voltages in HVdc grids[J], IEEE Transactions on Power Delivery, 33, 5, pp. 2254-2264, (2018)
  • [9] LIU Jian, TAI Nengling, FAN Chunju, Transient-voltagebased protection scheme for DC line faults in the multiterminal VSC-HVDC system[J], IEEE Transactions on Power Delivery, 32, 3, pp. 1483-1494, (2017)
  • [10] HE Jiawei, LI Bin, LI Ye, Et al., A fast directional pilot protection scheme for the MMC-based MTDC grid[J], Proceedings of the CSEE, 37, 23, pp. 6878-6887, (2017)