Asymmetrical voltage fault ride-through of wind turbine with DFIG using DVR

被引:0
|
作者
Ling Y. [1 ]
Dou Z. [2 ]
机构
[1] Department of Electrical Engineering, Shanxi Datong University, Datong
[2] Electric Power Research Institute, State Grid Shanghai Municipal Electric Power Company, Shanghai
关键词
Asymmetrical voltage fault; Doubly-Fed Induction Generator(DFIG); Dynamic Voltage Restorer(DVR); Fault ride-through; Wind power generation;
D O I
10.16081/j.issn.1006-6047.2019.02.010
中图分类号
学科分类号
摘要
Based on the characteristics that DVR(Dynamic Voltage Restorer) can restore voltage in a short time, the capability of DVR to assist DFIG(Doubly-Fed Induction Generator) wind turbines for the improvement of asymmetrical voltage fault ride-through is investigated. For DFIG wind turbines, the topology and compensation strategy of DVR are selected. The DVR control method based on proportional-resonant controller is analyzed and a single-loop voltage feedback control strategy is proposed. The simulation experiments are performed with PSCAD/EMTDC. Results show that DFIG wind turbines can successfully ride through asymmetrical voltage faults under DVR protection and its improved transient behaviors. © 2019, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:65 / 70and77
页数:7012
相关论文
共 21 条
  • [21] Jin K.M., Thinh Q.H., Kim E.H., DVR control of DFIG for compensating fault ride-through based on stationary and synchronous refe-rence frame, 7th International Power Electronics and Motion Control Conference(IPEMC), pp. 3004-3009, (2012)