Performance of refrigerants employed in rooftop air-conditioners

被引:3
作者
Suerdem, Kaan [1 ]
Taner, Tolga [2 ]
Acikgoz, Ozgen [3 ]
Dalkilic, Ahmet Selim [3 ]
Panchal, Hitesh [4 ]
机构
[1] Alarko Carrier Ind & Trade Co Inc, Gebze Organized Ind Zone, TR-41480 Gebze, Turkiye
[2] Aksaray Univ, Dept Motor Vehicles & Transportat Technol, TR-68100 Aksaray, Turkiye
[3] Yildiz Tech Univ, Fac Mech Engn, Dept Mech Engn, TR-34349 Istanbul, Turkiye
[4] Govt Engn Coll Patan, Dept Mech Engn, Katpur, Gujarat, India
来源
JOURNAL OF BUILDING ENGINEERING | 2023年 / 70卷
关键词
Refrigeration; EER; SEER; Life cycle climate performance; Rooftop air conditioner; LOW GWP; LCCP;
D O I
10.1016/j.jobe.2023.106301
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Unlike earlier studies, this study examines six refrigerants with various properties using the same rooftop air conditioning system of a building to evaluate performance. Performance metrics such as cooling capacity, energy consumption, temperature, and pressure were calculated. Laboratory testing of a rooftop air conditioner with R410a was performed to validate the simulation program's predicted data. Six distinct refrigerants' carbon emissions in two different scenarios were calculated using the Life Cycle Climate Performance technique, which was evaluated for environmental studies. These experimental tests were carried out at temperatures of 20 degrees C, 25 degrees C, 30 degrees C, and 35 degrees C, respectively. Maximum discrepancies between simulated and experimental results for cooling capacity, energy consumption, and energy efficiency were calculated to be 2.8%. The study found the lowest value in the R1234yf carbon emission at 51.30 kg CO(2)e. The highest cooling capacity was 154760.34 W in R454b, and the lowest cooling capacity was 76949.94 W in R1234yf. The highest EER value was 3,018 in R454b, while the lowest released was 2.257 in R22. The SEER value was 4.101 for R32 and 2.298 for R1234yf. The simulations concluded that R410a, R454b, and R32 refrigerants have superior cooling capacities.
引用
收藏
页数:19
相关论文
共 31 条
[1]  
[Anonymous], 2011, EU Commission Regulation, No 327/2011: Implementing Directive 2009/125/EC of the European Parliament and of the Council with Regard to Eco-Design Requirements for Fans Driven by Motors with an Electric Input Power between 125 W and 500 kW
[2]  
[Anonymous], 2017, EU commission regulation (EU) 2017/2195 of 23 november 2017 establishing a guideline on electricity balancing
[3]  
ANSI/AHRI, 2014, Standard 716 (SI): Performance Rating of Liquid Line Filters, VA
[4]  
ANSI/ASHRAE, 2019, Standard 37-2009 (RA 2019): Methods of Testing for Rating Electrically Driven Unitary Air -Conditioning and Heat -Pump Equipment
[5]   An experimental case study on the effect of condenser geometry in a refrigerator: Sub-cooling and coefficient of performance issues [J].
Borikar, Sanjaykumar A. ;
Borikar, Dilipkumar A. ;
Panchal, Hitesh ;
Cuce, Erdem ;
Dalkilic, Ahmet Selim ;
Alrubaie, Ali Jawad ;
Jaber, Mustafa Musa .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 148 :75-82
[6]   A case study on experimental and statistical analysis of energy consumption of domestic refrigerator [J].
Borikar, Sanjaykumar A. ;
Gupta, Mahendra M. ;
Alazwari, Mashhour A. ;
Malwe, Prateek D. ;
Moustafa, Essam B. ;
Panchal, Hitesh ;
Elsheikh, Ammar .
CASE STUDIES IN THERMAL ENGINEERING, 2021, 28
[7]  
British Standards Institution, 2016, BS EN 378-1:2016
[8]  
British Standards Institution, 2018, BS EN 14825:2018
[9]   Thermodynamic screening of alternative refrigerants for R290 and R600a [J].
Calleja-Anta, Daniel ;
Nebot-Andres, Laura ;
Catalan-Gil, Jesus ;
Sanchez, Daniel ;
Cabello, Ramon ;
Llopis, Rodrigo .
RESULTS IN ENGINEERING, 2020, 5
[10]   Life cycle climate performance evaluation (LCCP) on cooling and heating systems in South Korea [J].
Choi, Seyoung ;
Oh, Jinwoo ;
Hwang, Yunho ;
Lee, Hoseong .
APPLIED THERMAL ENGINEERING, 2017, 120 :88-98