Method for identification of grid operating conditions for adaptive overcurrent protection during intentional islanding operation

被引:26
作者
Ferreira, Roberta R. [1 ]
Colorado, Patry J. [1 ]
Grilo, Ahda P. [1 ]
Teixeira, Julio C. [1 ]
Santos, Ricardo C. [1 ]
机构
[1] CECS UFABC, Santo Andre, Brazil
关键词
Islanded operation; Synchronous distribution generator; Identification of operating conditions; Adaptive protection; DISTRIBUTED GENERATION;
D O I
10.1016/j.ijepes.2018.09.004
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Currently, it is considered that distributed synchronous generators may operate in intentional-islanding operation mode, in which a portion of the power grid, which consists of load and distributed generation, is isolated from the remainder of the utility system. However, the fault current level of the feeders drastically decreases when the utility grid is disconnected and the protection will not properly operate if the overcurrent settings are not changed. In this paper it is proposed a method for identification of the grid operating conditions, utility connected or islanded. The method is based on the use of a local scheme installed close to the protection device. The scheme uses a thyristor which is fired during a short waveform interval of voltage. The thyristor voltage and current are monitored and used to calculate the grid equivalent impedance. According to the grid equivalent impedance it is possible to determine whether the utility is connected or not. Simulations considering a distribution system and a distributed synchronous generator are used to validate the proposed method. The results show that the method can be used to update the protection settings when the operating condition of the system is changed from utility-connected to islanded operation mode or vice-versa. As a result, the method allows implementing an adaptive protection without the use of communication system or can be used as a backup to increase the resilience in case the communication is lost.
引用
收藏
页码:632 / 641
页数:10
相关论文
共 16 条
  • [1] [Anonymous], IEEE T POWER DELIV
  • [2] [Anonymous], 2008 IEEE EL POW EN
  • [3] [Anonymous], 2003, IEEE Std. 1547-2003, P1, DOI [10.1109/IEEESTD.2003.94285, DOI 10.1109/IEEESTD.2003.94285]
  • [4] [Anonymous], IEEE T IND ELECT
  • [5] [Anonymous], P 39 INT UPEC BRIST
  • [6] Barsali S, 2002, 2002 IEEE POWER ENGINEERING SOCIETY WINTER MEETING, VOLS 1 AND 2, CONFERENCE PROCEEDINGS, P789, DOI 10.1109/PESW.2002.985115
  • [7] Feasibility of adaptive intentional islanding operation of electric utility systems with distributed generation
    Caldon, Roberto
    Stocco, Andrea
    Turri, Roberto
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (12) : 2017 - 2023
  • [8] Control model for distributed generation and network automation for microgrids operation
    do Nascimento, Vinicius Cabral
    Lambert-Torres, Germano
    de Almeida Costa, Claudio Inacio
    Borges da Silva, Luiz Eduardo
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2015, 127 : 151 - 159
  • [9] Adaptive Protection and Microgrid Control Design for Hailuoto Island
    Laaksonen, Hannu
    Ishchenko, Dmitry
    Oudalov, Alexandre
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (03) : 1486 - 1493
  • [10] Automatic Reconnection From Intentional Islanding Based on Remote Sensing of Voltage and Frequency Signals
    Lessa Assis, Tatiana Mariano
    Taranto, Glauco Nery
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2012, 3 (04) : 1877 - 1884