Parameter Estimation for a 500 kV Overhead Transmission Line and Analysis of Dead Time Prior to Single-Phase Automatic Reclosing Based on Synchrophasor Measurements

被引:0
|
作者
Ivanov, I.E. [1 ]
Umnov, Ya. A. [1 ]
Lachugin, V.F. [2 ]
机构
[1] V. I. Lenin Ivanovo State Power Engineering University, Ivanovo, Russia
[2] JSC STS FGC UEC, Moscow, Russia
关键词
overhead transmission line; short circuit; equivalent circuit parameters; synchrophasor measurements; open circuit conditions;
D O I
10.1007/s10749-024-01791-1
中图分类号
学科分类号
摘要
The validation of equivalent circuit parameters for various power system components remains an important task in power system research. Overhead transmission line parameters available in data sheets may not be correct, particularly for lines having been operated for a long time. In addition, both series and shunt equivalent circuit line parameters can experience deviations as a result of different weather conditions and line loading. Synchrophasor measurements provide the possibility to carry out “passive” monitoring and collect data to compute equivalent circuit line parameters under various power system conditions. Phasor measurement units capturing data from lines operating at 330 kV and above process line currents and voltages (instead of busbar voltages). This provides for continuous monitoring of single-phase automatic reclosing. In this study, synchrophasor measurements are applied to estimate equivalent circuit parameters for the 500 kV Taman – Kubanskaya line as well as to thoroughly analyze a set of conditions on the line reflecting a short circuit followed by a successful line reclosing. All calculations and conclusions are formed on the basis of real data archives containing synchronized vectors of voltages and currents for single-sided switching modes of 500 kV Taman – Kubanskaya line, as well as a short circuit on this line with successful single-phase automatic reclosing. As a result, the capacitive conductivities of the direct and zero sequences, as well as the inductive impedance of the direct sequence were verified. In addition, vector diagrams in the dead time mode of line reclosing were constructed and analyzed in detail, as well as the criteria were considered, which made it possible to perform an a priori assessment of the success of automatic line reclosing according to the synchrophasor measurement data.
引用
收藏
页码:169 / 179
页数:10
相关论文
共 11 条
  • [1] Arcing time on the disconnected phase of a 500 KV overhead line during a single-phase automatic reclosing cycle
    Raskovalov Yu.V.
    Lir E.A.
    Power Technology and Engineering, 2010, 44 (1) : 83 - 86
  • [2] The Analysis of Overvoltage on 220kV Transmission Line in Single-phase Reclosing
    Cheng, Qiang
    Wang, Dong-qing
    Fan, Li-qin
    Liu, Xin-yuan
    2016 INTERNATIONAL CONFERENCE ON POWER, ENERGY ENGINEERING AND MANAGEMENT (PEEM 2016), 2016, : 25 - 31
  • [3] A METHOD FOR REDUCING DEAD TIME FOR SINGLE-PHASE RECLOSING IN EHV TRANSMISSION
    PETERSON, HA
    DRAVID, NV
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1969, PA88 (04): : 286 - &
  • [4] Reducing dead time for single-phase auto-reclosing on a series-capacitor compensated transmission line
    Tran-Quoc, T
    Hadj-Said, N
    Sabonnadière, JC
    Feuillet, R
    IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) : 51 - 56
  • [5] Arc effect on single-phase reclosing time of a UHV power transmission line
    Dudurych, IM
    Gallagher, TJ
    Rosolowski, E
    IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (02) : 854 - 860
  • [6] Arc effect on single-phase reclosing time of an UHV power transmission line
    Dudurych, I
    Gallagher, T
    Rosolowski, E
    2004 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1 AND 2, 2004, : 581 - 581
  • [7] SINGLE-PHASE AUTOMATIC RECLOSING CYCLE TESTS ON THE 1150 KV EKIBASTUZ-KOKCHETAV TRANSMISSION-LINE WITH SHUNT REACTORS
    BELYAKOV, NN
    DYAKOV, AF
    ILINICHNIN, VV
    NIKITIN, OA
    RASHKES, VS
    KHOROSHEV, MI
    ELECTRICAL TECHNOLOGY, 1989, (03): : 64 - 78
  • [8] Research on the 220kV Line Single-phase Reclosing Time Effect on the Stability of Power Grid
    Liu, Xinyuan
    Zhai, Xiaojia
    Zheng, Huiping
    Song, Shuyong
    PROCEEDINGS OF THE 2016 INTERNATIONAL CONFERENCE ON ENERGY, POWER AND ELECTRICAL ENGINEERING, 2016, 56 : 114 - 117
  • [9] Investigation of Single Phase Reclosing Using Arc Model on the 500 kV Transmission Line from Mae Moh to Tha Ta Ko
    Ngamsanroaj, K.
    Premrudeepreechacharn, S.
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 3595 - +
  • [10] Kalman- Filter Based Recursive Regression for Three-Phase Line Parameter Estimation using Synchrophasor Measurements
    Mishra, Chetan
    Centeno, Virgilio A.
    Pal, Anamitra
    2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2015,