Research on Asymmetric Fault Location of Wind Farm Collection System Based on Compressed Sensing

被引:0
|
作者
Yu H. [1 ]
Han G. [1 ]
Luo H. [2 ]
Wang H. [1 ]
机构
[1] KeyLaboratoryofModernPowerSystemSimulationandControl&RenewableEnergyTechnology, MinistryofEducation, Northeast Electric Power University, Jilin
[2] Qinhuangdao Power Supply Company, State Grid Jibei Electric Power Co., Ltd, Qinhuangdao
基金
中国国家自然科学基金;
关键词
compression sensing; convergence system; fault location; Offshore wind farm; ranging equation;
D O I
10.32604/ee.2023.028365
中图分类号
学科分类号
摘要
Aiming at the problem that most of the cables in the power collection system of offshore wind farms are buried deep in the seabed, which makes it difficult to detect faults, this paper proposes a two-step fault location method based on compressed sensing and ranging equation. The first step is to determine the fault zone through compressed sensing, and improve the data measurement, dictionary design and algorithm reconstruction: Firstly, the phase-locked loop trigonometric function method is used to suppress the spike phenomenon when extracting the fault voltage, so that the extracted voltage value will not have a large error due to the voltage fluctuation. Secondly,theλ-NIM dictionary is designed by using the node impedance matrix and the fault location coefficient to further reduce the influence of pseudo-fault points. Finally, the CoSaMP algorithm is improved with the generalized Jaccard coefficient to improve the reconstruction accuracy. The second step is to use the ranging equation to accurately locate the asymmetric fault of the wind farm collection system on the basis of determining the fault interval. The simulation results show that theproposed method is more accurate than the compressed sensing method and impedance method in fault section location and fault location accuracy, the relative error is reduced from 0.75% to 0.4%, and has a certain anti-noise ability. © 2023, Tech Science Press. All rights reserved.
引用
收藏
页码:2029 / 2057
页数:28
相关论文
共 50 条
  • [1] Fault Location Method of Wind Farm Collection Line Based on Vector Deviation Degree
    Zhang K.
    Sun L.
    Zhu Y.
    Liu X.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (10): : 127 - 133
  • [2] Research on VSC-HVDC fault location method based on compressed sensing
    Yu, Hua'nan
    Ma, Congcong
    Wang, He
    Liu, Weilin
    Du, Yao
    Bai, Xiaofei
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2020, 41 (03): : 158 - 166
  • [3] Research on Distribution Network Fault Location Based on Bayesian Compressed Sensing Theory
    Jia K.
    Li L.
    Yang Z.
    Zhao G.
    Bi T.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2019, 39 (12): : 3475 - 3485
  • [4] FAULT BRANCH LOCATION FOR MULTI-BRANCH COLLECTION LINES OF OFFSHORE WIND FARM
    Wang X.
    Wang Y.
    Liu Y.
    Gao X.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (01): : 163 - 170
  • [5] Combined fault location for single-phase grounding of wind farm collection line
    Peng H.
    Zhu Y.
    Yuan S.
    Yi Qi Yi Biao Xue Bao/Chinese Journal of Scientific Instrument, 2020, 41 (09): : 88 - 97
  • [6] Research on Collection System Optimal Design of Wind Farm with Obstacles
    Huang, W.
    Yan, B. Y.
    Tan, R. S.
    Liu, L. F.
    2017 2ND ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2017), 2017, 199
  • [7] An intelligent single-phase grounding fault location for a wind farm collection line based on an LSTM neural network
    Peng H.
    Wang W.
    Zhu Y.
    Gao H.
    Li R.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (16): : 60 - 66
  • [8] Fault location based on parameter estimation in hybrid transmission lines of wind farm
    Zhang, Ke
    Ma, Changxiao
    Cao, Yanqing
    Zhu, Yongli
    Zheng, Yanyan
    Gao, Jiacheng
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2020, 41 (08): : 323 - 329
  • [9] Research on the Fault Characteristics of HVDC with Wind Farm
    Bian, Erman
    Xu, Hongtao
    Kang, Chunlei
    Liu, Jin
    Wang, Zhe
    Fan, Shiyuan
    2017 IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2017,
  • [10] Fault handling for a wind farm with an internal DC collection grid
    Max, Lena
    Thiringer, Torbjorn
    Carlson, Ola
    WIND ENERGY, 2012, 15 (02) : 259 - 273