Analysis of Power Frequency Electrical Quantity and Line Selection Applicability for Two-Point Grounding Faults Occurring on Different Phases in Isolated Neutral System

被引:0
|
作者
Qi Z. [1 ]
Tian J. [2 ]
Xue Y. [1 ]
Cai Z. [1 ]
Xu B. [3 ]
机构
[1] New Energy College China, University of Petroleum (East China), Qingdao
[2] Guangxi Power Grid Power Dispatching Control Center, Nanning
[3] Research Center for Smart Grid, Shandong University of Technology, Zibo
关键词
Isolated neutral system; power frequency components; the steady-state line selection; two-point grounding faults occurring on different phases;
D O I
10.19595/j.cnki.1000-6753.tces.220473
中图分类号
学科分类号
摘要
In isolated neutral system, when two-point grounding faults occurring on different phases take place and at least one of the transition resistances is large, the outgoing protection with the small fault current can not be directly removed, it still need to rely on the line selection device to achieve protection. At present, there are some problems in the research on the two-point grounding fault of the small current grounding system, such as lack of quantitative analysis, lack of line selection effect analysis, and difficult to be applied in practice et al. To address these issues, based on the fault equivalent circuit, this paper analyzes the power frequency fault characteristics for two-point grounding faults occurring on different phases in isolated neutral system. Based on the fault characteristics, the adaptability of the existing power frequency line selection methods to the two-point grounding fault of the different phase is analyzed and the development suggestion of line selection technology is put forward. Firstly, Setting up the compound sequence network of two-point grounding faults occurring on different phases, using the nodal impedance matrixes to respectively deduce the expressions of power frequency components, such as two grounding fault point currents, zero-sequence voltage, and so on. Secondly, analyze the characteristics of two-point grounding fault power frequency electrical quantity with the change of the transition resistances in ungrounded systems and compare them with the characteristics of single-point grounding faults. Finally, according to the fault characteristics, the limitation of the existing line selection methods are analyzed, and the development ideas of two-point grounding fault line selection technology are put forward. The results show that, when the transition resistance of at least one fault point is large, the amplitudes of zero-sequence voltage and zero-sequence current of power frequency in two-point grounding of the different phase show the characteristics of single-point grounding. At least one fault feeder has a power frequency zero-sequence current amplitude greater than that of the healthy feeder. The phase relationship of zero-sequence current of power frequency between the fault feeder and health feeder depends on two fault phase sequences, transition resistance of two fault points and total capacitance to the ground of the system. Generally, there is no definite phase relationship. In general, the zero-sequence voltage amplitude when two fault points are grounded is between the zero-sequence voltage when two fault points are grounded separately. When the transition resistance of two fault points is similar, the zero-sequence voltage when two fault points are grounded is minimum. For two-point grounding faults occurring on different phases in isolated neutral system, the zero-sequence voltage starting criterion still has high resistance to transition resistance and can reach the threshold value in most cases. The zero-sequence current at the outlet of two fault lines generally does not conform to the characteristics of both fault feeder and healthy feeder, and the existing line selection principle is not fully applicable. When the amplitude and phase information are used for line selection, missing selection or rejection will occur. Development suggestions of line selection technology: (1) As for the development of steady-state line selection technology for two-point grounding fault, based on the conclusions of power frequency characteristics, the change of power frequency characteristics of faulty line and non-faulty line before and after subsequent fault, or the change of power frequency characteristics of faulty line and non-faulty line before and after first fault line removal can be further studied. According to the difference of power frequency characteristics between fault line and non-fault line in two stages, two-point grounding fault detection is realized and the detection time is further shortened to improve detection efficiency. (2) As for the development of transient line selection technology for two-point grounding fault, based on the conclusions of power frequency characteristics, the intermittent arc grounding process after subsequent fault can be analyzed. © 2023 Chinese Machine Press. All rights reserved.
引用
收藏
页码:3539 / 3551
页数:12
相关论文
共 28 条
  • [1] (2017)
  • [2] Xu Bingyin, Xue Yongduan, Feng Guang, Et al., Discussion on several problems of earthing fault protection in distribution network, Automation of Electric Power Systems, 43, 20, pp. 1-7, (2019)
  • [3] Topolanek D, Toman P, Ptacek M, Et al., Evaluation of different solutions of faulted phase earthing technique for an earth fault current limitation, CIRED - Open Access Proceedings Journal, 2017, 1, pp. 1107-1111, (2017)
  • [4] Wang Jianyuan, Zhu Yongtao, Qin Siyuan, Fault line selection method for small current grounding system based on directional traveling wave energy, Transactions of China Electrotechnical Society, 36, 19, pp. 4085-4096, (2021)
  • [5] Qin Suya, Xue Yongduan, Liu Lizheng, Et al., Transient characteristics and influence of small current grounding faults in active distribution network, Transactions of China Electrotechnical Society, 37, 3, pp. 655-666, (2022)
  • [6] Ding Xiaobing, Shi Zebing, Yu Jiang, Et al., Protection method of small current grounding system based on phase current variation, 2020 IEEE 4th Conference on Energy Internet and Energy System Integration (EI2), pp. 243-247, (2021)
  • [7] Wang Xiaowei, Liu Weibo, Guo Liang, Et al., High impedance fault line selection method based on inner product projection of different time periods for flexible grounding systems, Transactions of China Electrotechnical Society
  • [8] Yu Kun, Xu Pengbo, Zeng Xiangjun, Et al., Grounding fault line selection of distribution networks based on fuzzy measures integrated diagnosis, Transactions of China Electrotechnical Society, 37, 3, pp. 623-633, (2022)
  • [9] Zhang Mingyi, Sun Yuanzhang, Li Xiong, Et al., Application of improved time reversal algorithm in fault location for distribution network, Automation of Electric Power Systems, 45, 15, pp. 101-108, (2021)
  • [10] Ming Zhiqiang, Xu Hu, Fast line selection method of medium resistance in grounding system via arc suppression coil, Power System Technology, 33, 12, pp. 112-114, (2009)