Leakage current monitoring method for a long power cable in a substation based on a combined current criterion with self-compensation

被引:0
作者
Chen H. [1 ]
Liu H. [1 ]
Yao K. [1 ]
Ma Z. [2 ]
Sun X. [1 ]
机构
[1] State Grid Jiangsu Electric Power Company Maintenance Branch, Nanjing
[2] School of Information and Control Engineering, Qingdao University of Technology, Qingdao
来源
Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control | 2022年 / 50卷 / 12期
基金
中国国家自然科学基金;
关键词
combined current criteria; differential current; intelligent maintenance; leakage current monitoring; long power cable; residual current;
D O I
10.19783/j.cnki.pspc.211259
中图分类号
学科分类号
摘要
There is lack of an effective leakage current monitoring method for a long power cable in a substation. In this paper, based on the analysis on the variation features of leakage current and the imitation of present monitoring methods, a method for a substation AC system based on a combined current criterion with self-compensation is proposed. The residual current and the signal phase current of two ends of the power cable are used. The criterion is a combination of steady-state residual current, residual current increment, steady-state residual current differential, and single-phase residual current differential criteria, to achieve reliable detection on asymmetric leakage and three phase leakage currents of a long cable. The case study results show that the proposed method can monitor different kinds of leakage of a long power cable effectively and promote the level of AC system intelligent maintenance in a substation. © 2022 Power System Protection and Control Press. All rights reserved.
引用
收藏
页码:172 / 179
页数:7
相关论文
共 26 条
[1]  
ZHANG Chunyi, CHEN Nan, HUANG Yong, Electric fire detection equipment based on residual current, Fire Science and Technology, 32, 12, pp. 1385-1387, (2013)
[2]  
YU Dayang, ZHANG Congcong, WANG Lei, Et al., Study on the influence of power frequency magnetic field interference in substation on the accuracy of leakage current sensor, High Voltage Apparatus, 57, 6, pp. 107-114, (2021)
[3]  
WANG Xiaoming, LI Hongwen, GAO Qinxiang, Et al., Research on intelligent algorithm of residual current monitoring system for electrical fire prevention, Building Science, 25, 8, pp. 65-67, (2009)
[4]  
LI Jie, WANG Yingfen, LI Jiabao, Et al., Monitoring and positioning method of substation partial discharge signal based on ring topology, High Voltage Apparatus, 57, 8, pp. 136-141, (2021)
[5]  
WANG Xiaoming, LI Hongwen, GAO Qinxiang, Et al., Analysis on the application of residual current alarm and control system for electric fire prevention, Building Facilities Control & Management, 2, 6, pp. 64-67, (2008)
[6]  
YANG Xin, SUN Haotian, LIU Zhen, Et al., Test and calculation of short-circuit arc explosion wave energy of 220 kV high voltage cable joint, High Voltage Apparatus, 57, 10, pp. 44-49, (2021)
[7]  
YANG Liang, ZHOU Kai, NI Zhou, Et al., Analysis of XLPE cable insulation aging considering load characteristics, Smart Power, 48, 10, pp. 113-119, (2020)
[8]  
LI Guoqing, ZHANG Lin, JIANG Shouqi, Et al., Coordinated control strategies for DC fault ride-through of wind power integration via bipolar MMC-HVDC overhead lines, Power System Protection and Control, 49, 10, pp. 27-36, (2021)
[9]  
CHENG Mengzhu, ZHANG Xinhui, XU Mingming, Et al., Location method of an active distribution network fault section based on multi-target weighted grey target decision, Power System Protection and Control, 49, 11, pp. 124-132, (2021)
[10]  
XIA Yue, DU Songhuai, LI Chunlan, Et al., Development tendency of residual current protection technology and device in China, Transactions of the Chinese Society of Agricultural Engineering, 26, pp. 151-155, (2010)