Under-frequency load shedding scheme based on estimated inertia

被引:0
|
作者
Wang H. [1 ]
He P. [1 ]
Jiang Y. [1 ]
Wen B. [1 ]
机构
[1] College of Electrical Engineering and Automation, Fuzhou University, Fuzhou
基金
中国国家自然科学基金;
关键词
Frequency stability; Inertia calculation; Power shor-tage; Real-time calculation; Under-frequency load shedding;
D O I
10.16081/j.issn.1006-6047.2019.07.008
中图分类号
学科分类号
摘要
Different control methods for new energy power generation access to systems will bring different influences to the inertia of system. The real-time calculation method to calculate power shortage based on estimated inertia is proposed. Firstly, the shortcomings of the existing under-frequency load shedding equipment for calculating power shortage are analyzed. In view of these shortcomings, the influence of voltage deviation on active power balance is studied, and the quantization algorithm is proposed. According to the response information of load after disturbance, a real-time method to recognize system inertia is proposed. Then, the real-time calculation method to calculate power shortage based on estimated inertia is proposed. The simulative results of islanding system in IEEE 39-bus system verify the influence of the voltage offset on the calculation of power shortage, and the veracity and validity of recognizing system inertia and calculating power shortage in real-time. Compared with the traditional round-by-round load shedding schemes, the proposed scheme has relatively small amount of load shedding and dynamic frequency offset and stronger ability of frequency recovery. © 2019, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:51 / 56and63
页数:5612
相关论文
共 20 条
  • [1] Liu J., Yao W., Wen J., Et al., Prospect of technology for large-scale wind farm participating into power grid frequency regulation, Power System Technology, 38, 3, pp. 638-646, (2014)
  • [2] Xue Y., Lei X., Xue F., Et al., A review on impacts of wind power uncertainties on power systems, Proceedings of the CSEE, 34, 29, pp. 5029-5040, (2014)
  • [3] Kayikci M., Milanovic J.V., Dynamic contribution of DFIG-based wind plants to system frequency disturbances, IEEE Transactions on Power Systems, 24, 2, pp. 859-867, (2009)
  • [4] Holdsworth L., Ekanayake J.B., Jenkins N., Power system frequency response from fixed speed and doubly fed induction ge-nerator-based wind turbines, Wind Energy, 7, 1, pp. 21-35, (2004)
  • [5] Ding L., Yin S., Wang T., Et al., Integrated fre-quency control strategy of DFIGs based on virtual inertia and over-speed control, Power System Technology, 39, 9, pp. 2385-2391, (2015)
  • [6] Liu B., Yang J., Liao K., Et al., Improved frequency control strategy for DFIG-based wind turbines based on rotor kinetic energy control, Automation of Electric Power Systems, 40, 16, pp. 17-22, (2016)
  • [7] Zhang X., Yang L., Zhu X., Et al., Virtual rotational inertia control of PV generation system with energy storage devices, Electric Power Automation Equipment, 37, 9, pp. 109-115, (2017)
  • [8] Sigrist L., Egido I., Rouco L., Principles of a centralized UFLS scheme for small isolated power systems, IEEE Transactions on Power Systems, 28, 2, pp. 1779-1786, (2013)
  • [9] Yang D., Cai G., Load shedding control sensitivity and its applications in wide-area low-frequency protection, Electric Power Automation Equipment, 36, 3, (2016)
  • [10] Zhang B., Wang H., Yang S., Closed-loop control of power system transient stability(5): calculation of control quantity, Electric Power Automation Equipment, 34, 12, pp. 1-5, (2014)