High resistance single-phase grounding line selection in resonant grounding systems based on correlation detection

被引:0
|
作者
Liu J. [1 ]
Chen X. [2 ]
Zhang Z. [1 ,2 ]
Li [1 ]
机构
[1] State Grid Shaanxi Electric Power Research Institute, Xi'an
[2] School of Automation, Xi'an University of Technology, Xi'an
[3] Hebei Xuhui Electric Co., Ltd., Shijiazhuang
基金
中国国家自然科学基金;
关键词
correlation detection; cross correlation function; distribution networks; resonant grounding systems; single phase grounding (SPG); single phase grounding line selection;
D O I
10.19783/j.cnki.pspc.220005
中图分类号
学科分类号
摘要
To improve the level of limitation of high resistance single-phase grounding line selection in resonant grounding systems, a single-phase grounding line selection approach based on correlation detection is proposed. The compensation current of an arc suppression coil is modulated with a low-frequency square wave. The signal characteristics of fault and healthy lines after modulation are analyzed. The zero-sequence current of each line divided by the amplitude of zero sequence voltage enveloping is used for demodulation and correlation detection. A single-phase grounding line selection criterion based on a cross-correlation function is constructed and the influence of the selection of low-frequency modulated square wave frequency on line selection effect is analyzed and discussed. Simulation and experiments are carried out, the results of which show that it can accurately select the single-phase grounding line with a large high grounding resistance. © 2023 Power System Protection and Control Press. All rights reserved.
引用
收藏
页码:63 / 70
页数:7
相关论文
共 26 条
  • [1] (2009)
  • [2] ZENG Xiangjun, HUANG Hui, YU Kun, Et al., Voltage phase selection method for high resistance grounding and a single-phase disconnection fault of a distribution network based on flexible control of zero-sequence voltage, Power System Protection and Control, 50, 3, pp. 9-18, (2022)
  • [3] (2018)
  • [4] THERON J C J, PAL A, VARGHESE A., Tutorial on high impedance fault detection, 2018 71st Annual Conference for Protective Relay Engineers (CPRE), pp. 1-23, (2018)
  • [5] LIN Zhichao, LIU Xinxing, WANG Yingmin, Et al., Grounding fault protection based on zero sequence current comparison in low resistance grounding system, Power System Protection and Control, 46, 22, pp. 15-21, (2018)
  • [6] ZHANG B, SUN Y, SHI F, Et al., Detection of arc grounding fault in distribution network based on the harmonic component, 2018 13th IEEE Conference on Industrial Electronics and Applications (ICIEA), pp. 2559-2564, (2018)
  • [7] DHARMAPANDIT O, PATNAIK R K, DASH P K., A fast time-frequency response based differential spectral energy protection of AC microgrids including fault location, Protection and Control of Modern Power Systems, 2, 4, pp. 331-358, (2017)
  • [8] LIU B, MA H, XU H, Et al., Single-phase-to-ground fault detection with distributed parameters analysis in non-direct grounded systems, CSEE Journal of Power and Energy Systems, 5, 1, pp. 139-147, (2019)
  • [9] GONG Jing, Using wavelet packet decomposing coefficient to achieve distribution network single-phase ground fault line selection, Power System Protection and Control, 37, 24, pp. 94-99, (2009)
  • [10] LEI Yang, YANG Fan, WANG Yang, Et al., The flexible strategy of single-phase grounding fault in distribution network based on dual mode function, Distribution & Utilization, 37, 8, pp. 60-67, (2020)