Fault phase fast detection of the single-phase-to-ground fault in a power distribution network

被引:0
|
作者
Ye Y. [1 ]
Cai X. [2 ]
Xie M. [1 ]
Xu B. [3 ]
Wei L. [4 ]
机构
[1] Anhui Electric Power Dispatch Center, Hefei
[2] Shanghai Lanrui Electric Co., Ltd., Shanghai
[3] School of Electrical Engineering, Shanghai University of Electric Power, Shanghai
[4] Shanghai Sieyuan Electric Co., Ltd., Shanghai
来源
| 1600年 / Power System Protection and Control Press卷 / 49期
关键词
Fault phase detection; Fault phase voltage; Neutral voltage; Single-phase-to-ground fault;
D O I
10.19783/j.cnki.pspc.200360
中图分类号
学科分类号
摘要
In a power distribution network, the traditional single-phase-to-ground fault phase detection method needs to consider the phase sequence and amplitude of voltage to determine the fault phase. However, it is difficult to measure the phase angle in a high impedance grounded fault. As a result, it is more difficult to determine the fault phase. The relationship between the phase voltage and the neutral displacement voltage are analyzed when a single-phase grounded fault occurs in a small current grounded system. This paper proposes a simplified method to detect the fault phase directly and quickly according to the neutral displacement voltage and phase voltages. Finally, a simulation model is built in PSCAD/EMTDC, and the results show that the proposed method can accurately identify the fault phase in the case of different fault resistances. © 2021, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:96 / 103
页数:7
相关论文
共 36 条
  • [31] LI Xiaobo, LIU Baowen, WANG Chonglin, Zero-sequence voltage locus of resonant grounded system and its accurate control, Power System Technology, 37, 9, pp. 2669-2674, (2013)
  • [32] LIU Baowen, WANG Chonglin, LI Xiaobo, Analysis and application of zero-sequence voltage of single-phase ground fault asymmetrical system, Proceedings of the CSEE, 34, 28, pp. 4959-4967, (2014)
  • [33] MITOLO M, MUSCA R, TARTAGLIA M, Et al., Electrical safety analysis in the presence of resonant grounding neutral, IEEE Transactions on Industry Applications, 55, 5, pp. 4483-4489, (2019)
  • [34] WU Jun, ZHU Jun, SHEN Haiping, Et al., Analysis of the three-phase voltage unbalance computing formula used for distribution network, High Voltage Apparatus, 55, 12, pp. 211-214, (2019)
  • [35] CHEN Yanpu, ZHANG Jieqiu, Fast recursive algorithm for accurate measurement of power parameters, High Voltage Apparatus, 56, 8, pp. 250-255, (2020)
  • [36] ZHANG Jian, MA Wei, ZHU Yaqi, Et al., Research and design of neutral grounding resistance system for 10 kV distribution network, Power System Protection and Control, 47, 14, pp. 109-115, (2019)