Fast segregation of thermal response functions in short-term for vertical ground heat exchangers

被引:1
|
作者
Extremera-Jimenez, Alejandro J. [1 ]
Yousif, Charles [2 ]
Casanova-Pelaez, Pedro J. [3 ]
Cruz-Peragon, Fernando [1 ]
机构
[1] Univ Jaen, Higher Polytech Sch, Dept Mech & Min Engn, Campus Las Lagunillas S N, Jaen 23071, Spain
[2] Univ Malta, Inst Sustainable Energy, Barrakki St, Marsaxlokk 1531, Mxk, Malta
[3] Univ Jaen, Higher Polytech Sch, Dept Elect Engn & Automat, Campus Lagunillas S N, Jaen 23071, Spain
关键词
Ground Source Heat Pump (GSHP); Vertical Ground Heat Exchanger (VGHE); Short-term g-function (STGF); Borehole Thermal Resistance(Rb); Thermal Response Test (TRT); CFD Numerical Model; BOREHOLE; MODEL; TIME; PUMP; SIMULATION; RESISTANCE; DESIGN; SPACE; TESTS; FLUID;
D O I
10.1016/j.applthermaleng.2024.122849
中图分类号
O414.1 [热力学];
学科分类号
摘要
A detailed understanding of the short-term performance of the ground heat exchanger (GHE) is a major concern in the design of ground-source heat pumps (GSHP), as it has a significant impact in the efficiency and costs of the facility. The use of numerical models or artificial intelligence techniques may help in the short-term, although they are generally very time-consuming, becoming unpractical in numerous cases. The aim of this work is to obtain the thermal response factors according to the GHE, segregating the transient borehole behavior from the soil effect, based on a previous study which applies experimental data from thermal response tests (TRT) to the finite line source (FLS) model. The proposed method implies an extensive study of the fluid temperature as well as the development of new auxiliary thermal resistances related to the borehole and fluid, avoiding the implementation of numerical models. This procedure has been validated with the temperature outcomes of a 3D numerical model, obtaining low deviations, into a range of +/- 0.1 K, and mean absolute deviations below 0.01 K.
引用
收藏
页数:16
相关论文
共 50 条
  • [1] Modeling of vertical ground heat exchangers
    Koohi-Fayegh, Seama
    Rosen, Marc A.
    INTERNATIONAL JOURNAL OF GREEN ENERGY, 2021, 18 (07) : 755 - 774
  • [2] Examination of thermal interaction of multiple vertical ground heat exchangers
    Koohi-Fayegh, Seama
    Rosen, Marc A.
    APPLIED ENERGY, 2012, 97 : 962 - 969
  • [3] Thermal capacity effects in borehole ground heat exchangers
    Shirazi, Ali Salim
    Bernier, Michel
    ENERGY AND BUILDINGS, 2013, 67 : 352 - 364
  • [4] Comparative study on the thermal performance and economic efficiency of vertical and horizontal ground heat exchangers
    Cui, Qiliang
    Shi, Yu
    Zhang, Yulong
    Wu, Rui
    Jiao, Yifan
    ADVANCES IN GEO-ENERGY RESEARCH, 2023, 7 (01): : 7 - 19
  • [5] A new analytical model for short vertical ground heat exchangers with Neumann and Robin boundary conditions on ground surface
    Pan, Aiqiang
    Lu, Lin
    Tian, You
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2020, 152
  • [6] Extending capabilities of Thermal Response Tests in vertical ground heat exchangers: An experiment-based local short-time temperature response factor
    Cruz-Peragon, Fernando
    Casanova-Pelaez, Pedro J.
    Lopez-Garcia, Rafael
    Palomar-Carnicero, Jose M.
    APPLIED THERMAL ENGINEERING, 2020, 178
  • [7] Effective pipe-to-borehole thermal resistance for vertical ground heat exchangers
    Sharqawy, Mostafa H.
    Mokheimer, Esmail M.
    Badr, Hassan M.
    GEOTHERMICS, 2009, 38 (02) : 271 - 277
  • [8] Long-term study of vertical ground heat exchangers with varying seasonal heat fluxes
    Koohi-Fayegh, Seama
    Rosen, Marc A.
    GEOTHERMICS, 2018, 75 : 15 - 25
  • [9] Generic ground response functions for ground exchangers in the presence of groundwater flow
    Tye-Gingras, Maxime
    Gosselin, Louis
    RENEWABLE ENERGY, 2014, 72 : 354 - 366
  • [10] MATHEMATICAL MODELLING OF THERMAL AND FLOW PROCESSES IN VERTICAL GROUND HEAT EXCHANGERS
    Pater, Sebastian
    Ciesielczyk, Wlodzimierz
    CHEMICAL AND PROCESS ENGINEERING-INZYNIERIA CHEMICZNA I PROCESOWA, 2017, 38 (04): : 523 - 533