Active power coordinated stability control system for the industrial enterprise power grid

被引:0
|
作者
Nie L. [1 ]
Yin Y. [1 ]
Li Z. [1 ]
Li Q. [2 ]
Liu F. [1 ]
Yang Y. [3 ]
机构
[1] NARI Group Corporation/State Grid Electric Power Research Institute, Nanjing
[2] Xingyi Electric Power Co., Ltd., Xingyi
[3] Lanzhou Longneng Electric Power Science & Technology Ltd., Lanzhou
来源
Nie, Luyan (nieluyan@sgepri.sgcc.com.cn) | 1600年 / Power System Protection and Control Press卷 / 48期
关键词
Active power coordinated stability control system; Industrial enterprise power grid; Steam turbine fast valve;
D O I
10.19783/j.cnki.pspc.190948
中图分类号
学科分类号
摘要
In the context of energy conservation and emission reduction, self-supplied power plant units and energy-using equipment of ithe ndustrial enterprise power grid show a trend of increasing single-unit capacity. While improving the energy efficiency of enterprises, it also brings new challenges to the safe and stable operation of the enterprise power grid. This paper looks at the power balance control problem faced by industrial enterprise power grid, and proposes an adjustment method for industrial load to participate in active power balance and introduces a fast closing valve as a means of stability control. Finally, an overall scheme and implementation path of an active coordination control system are proposed. The rapid response of power and load enables fine control of the industrial enterprise power grid normal production and accident emergency, and provides technical support for improving the safe and stable operation level of the enterprise power grid and enterprise economic benefits. Engineering practice in an electrolytic aluminum enterprise power grid shows that this method is feasible. © 2020, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:133 / 140
页数:7
相关论文
共 23 条
  • [1] SUN Yuntao, SONG Yiqun, Peak load regulation trading mode for trans-provincial aid based on evaluation of system regulation capacity, Power System Protection and Control, 46, 4, pp. 86-91, (2018)
  • [2] ZHANG Wenliang, ZHOU Xiaoxin, YIN Yonghua, Et al., Composition and security analysis of "North China-Central, China-East China" UHV synchronous power grid, Proceedings of the CSEE, 30, 16, pp. 1-5, (2010)
  • [3] HUANG Yang, ZHANG Yiwei, MIN Yong, Et al., Security and stability characteristics and control strategies for isolated hydropower groups, Automation of Electric Power Systems, 36, 9, pp. 1-5, (2012)
  • [4] WANG Jiasheng, DENG Tongtian, RAN Jingchuan, Et al., Start-up and operational mode of fossil plant units in an isolated (little) power grid, Automation of Electric Power Systems, 32, 21, pp. 102-106, (2008)
  • [5] YE Jianzhong, ZOU Junxiong, LONG Fei, Et al., Research on frequency control strategy for isolated grid operation of thermal power unit in regional power network, Power System Protection and Control, 40, 7, pp. 123-128, (2012)
  • [6] WANG Yizhen, MA Shiying, WANG Qing, Present status and developing trend of research on over frequency in isolated power grid, Power System Technology, 36, 12, pp. 165-169, (2012)
  • [7] SHI Shanshan, LU Zongxiang, MIN Yong, Analysis on frequency characteristics of islanded microgrid, Automation of Electric Power Systems, 35, 9, pp. 36-41, (2011)
  • [8] HUANG Wei, NIU Ming, Analysis on non-planned isolated control strategy for microgrid, Automation of Electric Power Systems, 35, 9, pp. 42-46, (2011)
  • [9] LIU Yang, WANG Qian, GONG Kang, Et al., Transient stability control strategy of microgrid frequency based on SMES, Power System Protection and Control, 46, 15, pp. 101-108, (2018)
  • [10] YUAN Huling, LIU Fusuo, HOU Yuqiang, Et al., A tuning method for high-frequency protection program of fans considering emergency reserve and coordination with emergency control, Power System Protection and Control, 45, 7, pp. 77-83, (2017)