Calculation model and analysis of thermodynamic properties of R32 refrigerant

被引:0
|
作者
Qiu L. [1 ]
Gu B. [1 ]
Miao M. [1 ]
机构
[1] Institute of Refrigeration and Cryogenics Engineering, School of Mechanical Engineering, Shanghai Jiao Tong University, Shanghai
来源
Huagong Xuebao/CIESC Journal | 2019年 / 70卷 / 06期
关键词
Enthalpy; Entropy; Model; R32; refrigerant; State equation; Thermal performance;
D O I
10.11949/j.issn.0438-1157.20181528
中图分类号
学科分类号
摘要
The calculation model of the saturated vapor pressure and liquid density of R32 refrigerant in the saturation line (-130-78℃, 0.00013-5.76 MPa) is proposed. Based on this, the calculation model of latent heat of evaporation is derived. The state equation for P-v-T relationship in saturated line and superheated zone was established. Based on above model, the calculation models of enthalpy, entropy and specific heat capacity in saturated line and superheated region are obtained. The average relative errors of correlation models are less than 0.16% and maximum relative errors don􀆳t exceed 3.7% compared with data from REFPROP 9.0. The deviation of state equation is less than 8.7% compared with published equation and data. The average errors of enthalpy, entropy and specific heat capacity models derived from state equation and thermodynamic relation are less than 5.2%, and maximum relative errors of all calculation models are less than 9.1%. © All Right Reserved.
引用
收藏
页码:2075 / 2082
页数:7
相关论文
共 30 条
  • [1] Li L.S., Research progress on alternative refrigerants and their development trend, Journal of Refrigeration, 32, 6, pp. 53-58, (2011)
  • [2] Zhang Z.H., Chen J.L., Gao Y., Et al., Analysis on the influence of Kigali Amendment to Montreal Protocol to refrigeration and air-conditioning industry, Refrigeration and Air-conditioning, 17, 1, pp. 1-7, (2017)
  • [3] Shi L., Zhu M.S., Re-analysis on using R32 to substitute for R22 in household/commercial air-conditioning, Journal of Refrigeration, 31, 1, pp. 1-5, (2010)
  • [4] McLinden M.O., Lemmon E.W., Jacobsen R.J., Thermodynamic properties for the alternative refrigerants, International Journal of Refrigeration, 21, 4, pp. 322-338, (1998)
  • [5] Qv D., Dong B., Cao L., Et al., An experimental and theoretical study on an injection-assisted air-conditioner using R32 in the refrigeration cycle, Applied Energy, 185, pp. 791-804, (2017)
  • [6] Luo B., Theoretical study of R32 in an oil flooded compression cycle with a scroll machine, International Journal of Refrigeration, 70, pp. 269-279, (2016)
  • [7] Zhang Z., Tong L., Chang L., Et al., Energetic and exergetic analysis of an ejector-expansion refrigeration cycle using the working fluid R32, Entropy, 17, 7, pp. 4744-4761, (2015)
  • [8] Yang Z., Wu X., Yi H.J., Et al., Analysis on alternatives for HCFCS with low greenhouse effect, Journal of Refrigeration, 32, 1, pp. 1-6, (2011)
  • [9] Wu C., Li J., Numerical simulation of flow patterns and the effect on heat flux during R32 condensation in microtube, International Journal of Heat & Mass Transfer, 121, pp. 265-274, (2018)
  • [10] Chien N.B., Vu P.Q., Choi K.I., Et al., Boiling heat transfer of R32, CO<sub>2</sub> and R290 inside horizontal minichannel, Energy Procedia, 105, pp. 4822-4827, (2017)