Integrated application of software and hardware phase-locked loop on grid connection control for distributed wind power

被引:0
作者
Zhu J. [1 ]
Gu J. [1 ]
Meng B. [1 ]
Cao S. [1 ]
Ren H. [1 ]
机构
[1] Institute of Electrical Engineering, Nantong University, Nantong
来源
Taiyangneng Xuebao/Acta Energiae Solaris Sinica | 2022年 / 43卷 / 01期
关键词
Distributed power; Grid-connected control; Phase-locked loop; Signal processing and detection; Software and hardware combination;
D O I
10.19912/j.0254-0096.tynxb.2020-0115
中图分类号
学科分类号
摘要
Firstly, a grid-connected control design scheme is proposed innovatively combined software and hardware. Secondly, in the design of phase-locked loop(PLL), simulation and programming are carried out from aspects of hardware PLL and software PLL. The dual second order generalized integral phase-locked loop(DSOGI-PLL) is selected as the grid voltage signal acquisition technology in the control of small double-fed wind power (DFWG), and the corresponding program algorithm is developed to obtain the fundamental signal by DSP2812 microcontroller, which is used in actual the stator voltage orientation control of the DFWG system, realizing the reliability and anti-disturbance of the control target. Finally, combined with the voltage comparison signal of the grid side and the generator stator side, a hardware PLL is applied, the expected design goals are achieved through system joint debugging, the voltage difference between the grid side and the generator side is controlled within 2 Hz, the phase difference within 12°, and the RMS difference within 4 V, the design results are complied with national industry standards and have practical industry application value. © 2022, Solar Energy Periodical Office Co., Ltd. All right reserved.
引用
收藏
页码:36 / 43
页数:7
相关论文
共 14 条
[1]  
ZHENG Z, YANG G, GENG H., Coordinated control of a doubly-fed induction generator based wind farm and a static synchronous compensator for low voltage ride-through grid code compliance during asymmetrical grid faults, Energies, 6, 9, pp. 4660-4681, (2013)
[2]  
LIANG J B., Analysis of parallel-in technology of wind power and power quality control strategy, Electrotechnics, 12, pp. 69-70, (2018)
[3]  
ZHENG C, LI S X, LI H L, Et al., Electromechanical transient simulation model of double fed induction generator and disturbed characteristic of scale wind/photovoltaic hybrid system, High voltage technology, 43, 3, pp. 1023-1033, (2017)
[4]  
YE H Y., Wind turbine monitoring and control, pp. 1-4, (2011)
[5]  
ZHANG H, ZHANG Y C, YANG D W., Two-vectors-based model predictive direct power control of doubly fed induction generator for grid connection and power regulation, Transactions of China Electrotechnical Society, 31, 5, pp. 69-76, (2016)
[6]  
ZHANG Z Y, WANG P G., Grid-connected harmonic current suppression of permanent magnet direct drive wind power converter based on current cross-coupling control, IEEE access, 8, pp. 43497-43507, (2020)
[7]  
ELTAMALY A M, Al-SAUD M S, ABO-KHALIL A G., Dynamic control of a DFIG wind power generation system to mitigate unbalanced grid voltage, IEEE access, 8, pp. 39091-39103, (2020)
[8]  
FILIPOVIC F, PETRONILEVIC M, MITROVIC N, Et al., A novel repetitive control enhanced phase-locked loop for synchronization of three-phase grid-connected converters, Energies, 13, 1, pp. 1-25, (2019)
[9]  
DIDA A, MERAHI F, MEKHILEF S., New grid synchronization and power control scheme of doubly-fed induction generator based wind turbine system using fuzzy logic control, Computers and electrical engineering, 84, (2020)
[10]  
WANG Z W, SHEN C, LIU F., Analysis on impact of doubly fed induction generations with different phase lock mechanism on power system small signal stability, Proceedings of the CSEE, 34, 34, pp. 6167-6176, (2014)