Time domain distance protection of new energy transmission line grounding fault considering the phase difference of zero sequence current on both sides of the fault point

被引:0
|
作者
Ye Y. [1 ]
Wang J. [1 ]
Wang S. [1 ]
Zhang R. [2 ]
Liu S. [2 ]
Zheng T. [2 ]
Su Y. [2 ]
机构
[1] State Grid Anhui Electric Power Limited Company, Hefei
[2] Beijing Sifang Engineering Co., Ltd., Beijing
来源
Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control | 2023年 / 51卷 / 20期
关键词
current phase difference; new energy transmission line; time domain distance protection; transition resistance; zero sequence current;
D O I
10.19783/j.cnki.pspc.236141
中图分类号
学科分类号
摘要
The fault current in new energy power supply presents weak feedback, strong controllability and a large number of interharmonics. This leads to decline in the reliability of existing power frequency distance protection. Time-domain distance protection mainly establishes the fault distance based on the equation, and is less affected by the short-circuit current characteristics of new energy. This paper proposes an improved time domain distance protection scheme for new energy transmission lines that takes into account the phase difference of zero sequence current on both sides of the fault point. This is to address the issue of significant deviation in the calculation of fault distance caused by the influence of distributed capacitance on the phase of zero sequence current when the new energy transmission line is long. First, taking into account the influence of the phase difference of the zero sequence current on both sides of the fault point, the transition resistance is equivalent to the transition impedance. Then, by writing the fault circuit equation and finding the fault distance, a protection criterion is formed. Finally, based on a large number of simulation experiments using PSCAD/EMTDC, it is verified that the time-domain distance protection scheme proposed in this paper has only a small error in calculating the fault distance, and can be well applied to scenarios where new energy is transmitted through medium to long distance AC lines. © 2023 Power System Protection and Control Press. All rights reserved.
引用
收藏
页码:180 / 187
页数:7
相关论文
共 23 条
  • [1] WEN Jinyu, ZHOU Bo, WEI Lishen, Preliminary study on an energy storage grid for future power system in China, Power System Protection and Control, 50, 7, pp. 1-10, (2022)
  • [2] ZHUO Zhenyu, ZHANG Ning, XIE Xiaorong, Et al., Key technologies and developing challenges of power system with high proportion of renewable energy, Automation of Electric Power Systems, 45, 9, pp. 171-191, (2021)
  • [3] WEN Zhiwen, JIA Ke, YU Lei, Et al., High speed protection based on time-frequency characteristic similarity for a Teed transmission line connected to renewable energy power plants, Power System Protection and Control, 51, 4, pp. 1-11, (2023)
  • [4] ZENG Xiang, WEN Minghao, QIAN Kun, Et al., Influence of inverter-interfaced distributed generation integration on grounding distance protection and its strategies, Smart Power, 51, 1, pp. 46-53, (2023)
  • [5] ZHENG Bowen, WANG Zengping, LU Zhe, Et al., Research on transient-based relay protection, Power System Protection and Control, 48, 22, pp. 18-25, (2020)
  • [6] ZHONG Xian, FAN Yanfang, CHEN Weiwei, Et al., Study on LVRT coordinate control strategy of DFIG when considering non-rotor side crowbar protection, JCIS, 11, 18, pp. 6747-6757, (2015)
  • [7] GUO Jinxue, NAN Dongliang, HAO Hongyan, Et al., Effects of PV power station on distance protection and automatic reclosing, Electrical Engineering, 11, pp. 25-31, (2017)
  • [8] BI Tianshu, LI Yanbin, MA Lihong, Et al., Configuration and setting of relay protection for wind farm and its outgoing line, Power System Protection and Control, 42, 5, pp. 45-50, (2014)
  • [9] ZHANG Taisheng, HAN Wei, YANG Lin, Et al., Time-domain distance protection for transmission lines of doubly-fed wind farms based on waveform correlation analysis, Power System Protection and Control, 49, 14, pp. 82-88, (2021)
  • [10] BU Qiangsheng, GAO Lei, SONG Liangliang, Et al., Short circuit current and voltage frequency inconsistency in wind farm and its effect on distance protection and relay protection test, Power System Protection and Control, 43, 8, pp. 21-27, (2015)