Solid Desiccant Heat Pump Fresh Air Unit using Composite Silica Gel

被引:0
作者
Yang, Tianyu [1 ]
Guo, Defang [2 ]
Ge, Tianshu [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Key Lab Power Mech Engn, MOE China, Shanghai 200240, Peoples R China
[2] Qingdao Haier A C Elect Co Ltd, Qingdao 266101, Peoples R China
基金
中国国家自然科学基金;
关键词
fresh air system; desiccant coated heat exchanger; humidification; dehumidification; experimental comparison; PERFORMANCE EVALUATION; PIPE ARRAY; EXCHANGER; VENTILATION; RECOVERY; SYSTEMS;
D O I
10.1007/s11630-024-1964-6
中图分类号
O414.1 [热力学];
学科分类号
摘要
The introduction of fresh air into the indoor space leads to a significant increase in cooling or heating loads. Solid desiccant heat pump fresh air unit which can handle the latent and sensible load of fresh air efficiently have been proposed recently. To improve the performance of the solid desiccant heat pump fresh air unit in the fresh air handling process, in this paper, the application of composite silica gel in a heat pump fresh air unit was investigated. The comparison between silica gel coating (SGC) and composite silica gel coating (CSGC) shows that the adsorption rate and water uptake capacity of CSGC are more than two times higher than those of SGC. An experimental setup for the solid desiccant heat pump fresh air unit was established. The performance of SGC and CSGC was tested in the setup successively. Results show that under summer conditions, compared with the solid desiccant heat pump fresh air unit using silica gel (SGFU), the average moisture removal and COP of the one using composite silica gel (CSGFU) increased by 15% and 30%, respectively. Under winter conditions, compared with SGFU, the average humidification and COP of CSGFU increased by 42% and 17%. With optimal operation conditions of 3 min switchover time and 40 r/s compressor frequency, the COP of CSGFU under summer conditions can reach 7.6. Results also show that the CSGFU and SGFU have higher COP and dehumidification rate under higher outdoor temperature and humidity ratio.
引用
收藏
页码:1286 / 1300
页数:15
相关论文
共 42 条
  • [1] Modelling condensation in energy exchangers with variable permeability membranes
    Abadi, Iman Rahgozar
    Aminian, Behzad
    Nasr, Mohammad Rafati
    Huizing, Ryan
    Green, Sheldon
    Rogak, Steven
    [J]. ENERGY AND BUILDINGS, 2022, 262
  • [2] Thermal performance of building-integrated horizontal earth-air heat exchanger in a subtropical hot humid climate
    Ahmed, Shams Forruque
    Khan, M. M. K.
    Amanullah, M. T. O.
    Rasul, M. G.
    Hassan, N. M. S.
    [J]. GEOTHERMICS, 2022, 99
  • [3] Experimental investigation of counter flow heat exchangers for energy recovery ventilation in cooling mode
    Al-Zubaydi, Ahmed Y. Taha
    Hong, Guang
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 93 : 132 - 143
  • [4] An intense review on the latest advancements of Earth Air Heat Exchangers
    Bordoloi, Namrata
    Sharma, Aashish
    Nautiyal, Himanshu
    Goel, Varun
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 89 : 261 - 280
  • [5] Effect of pore size on the performance of composite adsorbent
    Bu, Xianbiao
    Wang, Lingbao
    Huang, Yuanfeng
    [J]. ADSORPTION-JOURNAL OF THE INTERNATIONAL ADSORPTION SOCIETY, 2013, 19 (05): : 929 - 935
  • [6] Experimental investigation on a fresh air dehumidification system using heat pump with desiccant coated heat exchanger
    Chai, Shaowei
    Sun, Xiangyu
    Zhao, Yao
    Dai, Yanjun
    [J]. ENERGY, 2019, 171 : 306 - 314
  • [7] Experimental analysis on energy recovery ventilator with latent heat exchanger using hollow fiber membrane
    Cho, Hye-Jin
    Cheon, Seong-Yong
    Jeong, Jae-Weon
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2023, 278
  • [8] Properties of aqueous solutions of lithium and calcium chlorides: formulations for use in air conditioning equipment design
    Conde, MR
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2004, 43 (04) : 367 - 382
  • [9] Experimental study on the heat recovery characteristic of a heat exchanger based on a flat micro-heat pipe array for the ventilation of residential buildings
    Diao, Y. H.
    Liang, L.
    Kang, Y. M.
    Zhao, Y. H.
    Wang, Z. Y.
    Zhu, T. T.
    [J]. ENERGY AND BUILDINGS, 2017, 152 : 448 - 457
  • [10] Performance evaluation of a desiccant coated heat exchanger with two different desiccant materials
    Erkek, Turkan Ucok
    Gungor, Ali
    Fugmann, Hannes
    Morgenstern, Alexander
    Bongs, Constanze
    [J]. APPLIED THERMAL ENGINEERING, 2018, 143 : 701 - 710