INVESTIGATION OF IMPEDANCE-DIFFERENTIAL PROTECTION’S ALGORITHM AS A FAULT LOCATOR FOR DOUBLE-CIRCUIT TRANSMISSION LINE

被引:0
作者
Herlender J. [1 ]
Izykowski J. [1 ]
Brusilowicz B. [1 ]
机构
[1] Wroclaw University of Science and Technology, Wroclaw
来源
Technical Electrodynamics | 2020年 / 2020卷 / 06期
关键词
algorithm; ATP-EMTP; double-circuit line; fault location; negative and zero sequences; simulation; transmission line;
D O I
10.15407/techned2020.06.057
中图分类号
学科分类号
摘要
This paper deals with an analysis of impedance-differential protection algorithm applied to locate faults on a double-circuit transmission line. In particular, the study of fault location accuracy for the case of using the relation between currents for negative-sequence not for zero-sequence, as it was presented so far, is provided. It results from the well-known fact that zero-sequence impedances are in practice considered as quite unreliable data. Therefore, one has to limit usage of zero-sequence impedance parameters as much as possible. Such approach was applied in this paper and therefore theuse of the additional relation of currents for negative-sequence is under investigation. The fault signals from ATP-EMTP simulation on the sample double-circuit transmission line was applied for evaluating the fault location accuracy. References 8, figures 4, table 1. © J. Herlender
引用
收藏
页码:1 / 3
页数:2
相关论文
共 8 条
[1]  
Premalata J., Ashokkumar P., An integrated approach for directional relaying of the double-circuit line, IEEE Trans. Power Del, 26, pp. 1783-1792, (2011)
[2]  
Eissa M.M., Masoud M., A novel digital distance relaying technique for transmission line protection, IEEE Trans. Power Del, 16, 3, pp. 380-384, (2001)
[3]  
Bhalja B., Maheshwari R., High-resistance faults on two terminal parallel transmission line: Analysis, simulation studies, and adaptive distance relaying scheme, IEEE Trans. Pow. Del, 22, 2, pp. 801-812, (2007)
[4]  
Bolandi T.G., Seyedi H., Hashemi S.M, Nezhad P.S., Impedance-differential protection: A new approach to transmission line pilot protection, IEEE Trans. Power Del, 30, 6, pp. 2510-2517, (2015)
[5]  
Hinge T., Dambhare S., Synchronised/unsynchronised measurements based novel fault location algorithm for transmission line, IET Generation, Transmission & Distribution, 12, 7, pp. 1493-1500, (2018)
[6]  
Solak K., Herlender J., Izykowski J., Transmission line impedance-differential protection with improved stabilization for external fault cases, 19th Intern. Sc. Conf. on Electric Power Engineering(EPE), (2018)
[7]  
Herlender J., Solak K., Izykowski J., Impedance-Differential Protective Algorithm for Double-Circuit Transmission Lines, Przeglad elektrotechniczny, 11, pp. 238-242, (2019)
[8]  
Hoidalen H.K., Prikler L., Hall J.L., - The graphical preprocessor to ATP, (2016)