Effects of VSC-HVDC on Receiving-end System Strength of LCC-HVDC

被引:0
|
作者
Xia C. [1 ]
Wang Z. [1 ,2 ]
Zhou B. [3 ]
Nie J. [3 ]
Hong C. [3 ]
机构
[1] School of Electric Power, South China University of Technology, Guangzhou, 510640, Guangdong Province
[2] Electric Power Research Institute of State Grid Jiangsu Electric Power Co. Ltd., Nanjing, 211103, Jiangsu Province
[3] Electric Power Research Institute of CSG, Guangzhou, 510663, Guangdong Province
来源
基金
中国国家自然科学基金;
关键词
LCC-HVDC; RVSF; Short circuit ratio; System strength; VSC-HVDC;
D O I
10.13335/j.1000-3673.pst.2018.1750
中图分类号
学科分类号
摘要
The effect of receiving-end-system voltage strength factor (RVSF) on characteristics and operation modes of different power system components in end-to-end system can be used as a index of the strength of the receiving system to study the effect of VSC-HVDC on strength of LCC-HVDC end-to-end system in a hybrid dual feed system. In order to facilitate research, analytical calculation method of RVSF under different control modes of VSC-HVDC is proposed. The RVSF values of VSC-HVDC in different control modes, and active power and reactive power of different transmission and different drop points are calculated, and the influence of these factors on the strength of LCC-HVDC receiving end system is analyzed. The conclusion can play a guiding role for planning and operation of hybrid multi-infeed system containing VSC-HVDC and LCC-HVDC. © 2019, Power System Technology Press. All right reserved.
引用
收藏
页码:2031 / 2038
页数:7
相关论文
共 17 条
  • [1] Liu T., Li J., Li M., Et al., Control and protection system design of Luxi back-to-back asynchronous interconnection HVDC project of China Southern Power Grid, Southern Power System Technology, 8, 6, pp. 18-22, (2014)
  • [2] Yang Y., Lin Y., Xu W., Et al., Influence of Wudongde multi-terminal HVDC on security and stability of Guangdong power grid, Guangdong Electric Power, 30, 11, pp. 44-50, (2017)
  • [3] Rao H., Hong C., Zhou B., Et al., Study on improvement of VSC-HVDC at inverter side of Wudongde multi-terminal UHVDC for the problem of centralized multi-infeed HVDC, Southern Power System Technology, 11, 3, pp. 1-5, (2017)
  • [4] Xin H., Zhang F., Yu Y., Et al., Generalized short circuit ratio for multi-infeed DC systems: definition and theoretical analysis, Proceedings of the CSEE, 36, 3, pp. 633-647, (2016)
  • [5] Jin X., Zhou B., Guan L., Et al., HVDC-interaction-strength index for the multi-infeed-HVDC power system, Automation of Electric Power Systems, 33, 15, pp. 98-102, (2009)
  • [6] Lin W., Tang Y., Guo X., Study on voltage stability of multi-infeed HVDC power transmission system, Power System Technology, 35, 8, pp. 64-68, (2011)
  • [7] Aik D.L.H., Andersson G., Influence of load characteristics on the power/voltage stability of HVDC systems. II.Stability Margin sensitivity, IEEE Transactions on Power Delivery, 13, 4, pp. 1445-1452, (1998)
  • [8] Xu Z., Characteristics of HVDC connected to weak AC systems part1: HVDC transmission capability, Power System Technology, 21, 1, pp. 12-16, (1997)
  • [9] Hong C., Rao H., The index parameters for analyzing multi-infeed HVDC systems and their applications, Southern Power System Technology, 2, 4, pp. 37-41, (2008)
  • [10] Zhang Y., Su Y., Guan L., Evaluation voltage supporting strength of receiving-end power grid of HVDC transmission system in environment of AC/DC parallel power system and asynchronously interconnected power grid, Power System Technology, 36, 1, pp. 90-95, (2012)