Research Status and Prospect of High Voltage Vacuum Circuit Breaker

被引:0
|
作者
Zhong J. [1 ]
Sun G. [2 ]
Yang B. [3 ]
Zhao X. [2 ]
Li X. [2 ]
Ma C. [2 ]
Jia H. [1 ]
Zhang X. [4 ]
机构
[1] China Electrical Equipment Group Science and Technology Research Institute Co., Ltd., Shanghai
[2] Pinggao Group Co., Ltd., Pingdingshan
[3] Henan High Voltage Apparatus Research Institute Co., Ltd., Pingdingshan
[4] School of Electical Engineering, Shenyang University of Technology, Shenyang
关键词
large capacity; reliability; SF6 alternative technology; single-break vacuum interrupter; vacuum interrupting technology;
D O I
10.13336/j.1003-6520.hve.20232381
中图分类号
学科分类号
摘要
In view of the development needs of green power grid, the characteristics of SF6 complete substitution technology and partial substitution technology route and related technologies are summarized and compared, and it is pointed out that vacuum interrupting technology is an effective means for green and low-carbon development of power grid. Comparing and analyzing the technical characteristics and research status of multi-break vacuum circuit breakers at this stage, we believe that single-break vacuum circuit breakers have significant advantages in terms of structure and reliability.At present, the commercial single-break vacuum interrupter has been developed to 145 kV/40 kA, and the research status and future development trend of high-voltage and high-current single-break vacuum interrupter indoor and outdoor insulation technology, arc morphological evolution law and opening and closing control, temperature rise characteristics and welding quality stability of vacuum interrupter are reviewed. The results show that the pressure equalization design of the vacuum gap inside the vacuum interrupter and the “saturation” of the insulation of the long vacuum gap are the key factors restricting the increase of the voltage of the interrupter; The preparation of the ablation-resistant contact material and the design of the magnetic field are very important for the formation process of anode spots on the contact surface and the matching of the opening and closing speed of the vacuum circuit breaker; Selecting the contact structure with low loop resistances and optimizing the heat dissipation structure of the vacuum circuit breaker can effectively improve the rated current capacity of the vacuum interrupter; In addition, the influencing factors of vacuum interrupter welding quality and stability are summarized, and it is pointed out that the ceramics metallization and selection of appropriate brazing temperature and solder can significantly improve the welding strength. Finally, it is pointed out that vacuum circuit breakers tend to develop with characteristics of large-capacity, miniaturization, intelligence, low-overvoltage, maintenance-free, specialization and multi-function. © 2024 Science Press. All rights reserved.
引用
收藏
页码:451 / 466
页数:15
相关论文
共 92 条
  • [21] CHENG Xian, LI Xin, GE Guowei, Et al., Insulation configuration and optimization of integrated voltage self-sharing interrupter for series connection, High Voltage Engineering, 48, 3, pp. 820-828, (2022)
  • [22] BETZ T, KONING D., Influence of grading capacitors on the breaking capacity of two vacuum interrupters in series, IEEE Transactions on Dielectrics & Electrical Insulation, 6, 4, pp. 405-409, (1999)
  • [23] ZOU Jiyan, LIANG Deshi, HUANG Chongyang, Et al., Synchronous control of module series connection interruption in 110 kV DC vacuum circuit breaker, High Voltage Engineering, 46, 8, pp. 2627-2634, (2020)
  • [24] ZENG Xianghao, ZHANG Haichuan, LIAO Minfu, Et al., Restrictive asynchronous breaking strategy of multi-break VCB with fiber controlled module, High Voltage Apparatus, 57, 2, pp. 1-6, (2021)
  • [25] XIE Jiuming, Research on mechanical properties and synchronous control for 126 kV high voltage vacuum circuit breaker, (2017)
  • [26] QIU Jin, CHEN Xuanshu, CHEN Jiangbo, Et al., Design and implementation of synchronization control system for multi-break vacuum circuit breaker, Electric Power Automation Equipment, 32, 11, pp. 150-154, (2012)
  • [27] LIU Zhaojin, Research and design of multi-break vacuum circuit breaker synchronous control system, (2017)
  • [28] OKUBO H., Development of electrical insulation techniques in vacuum for higher voltage vacuum interrupters, 2006 International Symposium on Discharges and Electrical Insulation in Vacuum, pp. 7-12, (2006)
  • [29] MIYAZAKI F, INAGAWA Y, KATO K, Et al., Electrode conditioning characteristics in vacuum under impulse voltage application in non-uniform electric field, IEEE Transactions on Dielectrics and Electrical Insulation, 12, 1, pp. 17-23, (2005)
  • [30] SATO S, KOYAMA K., Effect of mechanical polish of electrode on several breakdown characteristics of vacuum gap, 20th International Symposium on Discharges and Electrical Insulation in Vacuum, pp. 427-430, (2002)