Inverse-time current protection method of a microgrid based on a composite fault compensation factor

被引:0
作者
Cao Z. [1 ]
Ji L. [1 ]
Chang X. [2 ]
Shi J. [1 ]
Zhu L. [1 ]
Zhang L. [1 ]
Bao Z. [1 ]
机构
[1] School of Electrical Engineering, Shanghai University of Electric Power, Shanghai
[2] State Grid Electric Power Research Institute of Shanxi Electric Power Company, Taiyuan
来源
Ji, Liang (jihome2002@sina.cn) | 1600年 / Power System Protection and Control Press卷 / 48期
基金
中国国家自然科学基金;
关键词
BAS algorithm; Coordination optimization; Inverse-time overcurrent protection; Inverter interfaced DG; Microgrid;
D O I
10.19783/j.cnki.pspc.191495
中图分类号
学科分类号
摘要
In order to solve the problem of the influence of an inverter interfaced Distributed Generation (DG) on the speed and coordination of microgrid protection, an improved inverse-time microgrid current protection method based on composite fault compensation factor and a Beetle Antenna Search (BAS) algorithm is proposed. First, by analyzing the voltage distribution characteristics of the protection installation at the time of the fault and combining the characteristics of the measured impedance, a composite fault compensation factor is constructed. This solves the problem of long time delay caused by the short-circuit current changes in inverse-time overcurrent protection and improves the speed of protection. In addition, in order to solve the problem of microgrid protection coordination caused by factors such as DG access and changes in the operation mode of microgrids, the BAS algorithm is used to optimize the parameters of improved inverse-time overcurrent protection to ensure the coordination and cooperation of adjacent protections. Finally, a microgrid simulation model is built in DIgSILENT/PF software to verify the effectiveness of the improved method. The simulation results show that compared with the traditional inverse-time overcurrent protection, the improved protection method significantly improves the speed performance and meets the coordination requirements under different operating modes and fault conditions of the microgrid. © 2020, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:133 / 140
页数:7
相关论文
共 28 条
  • [11] LI Yongli, JIN Qiang, LI Botong, Et al., Application of inverse-time overcurrent protection based on low voltage acceleration in micro-grid, Journal of Tianjin University, 44, 11, pp. 955-960, (2011)
  • [12] DEHGHANPOUR E, KAREGAR H, KHEIROLLAHI R, Et al., Optimal coordination of directional over-current relays in microgrids by using cuckoo-linear optimization algorithm and fault current limiter, IEEE Transactions on Smart Grid, 9, 2, pp. 1365-1375, (2018)
  • [13] HUANG Wentao, TAI Nengling, YANG Xia, Inverse-time low-impedance protection scheme for microgrids, Proceedings of the CSEE, 34, 1, pp. 105-114, (2014)
  • [14] JIANG Bin, MU Longhua, GUO Wenming, Et al., Microgrid protection based on change of measured bus admittance, Power System Technology, 39, 6, pp. 1751-1758, (2015)
  • [15] KAR S, SAMANTARAY S R, ZADEH M D., Data-mining model based intelligent differential microgrid protection scheme, IEEE Systems Journal, 11, 2, pp. 1161-1169, (2017)
  • [16] MISHRA M, ROUT P K., Detection and classification of micro-grid faults based on HHT and machine learning techniques, IET Generation, Transmission & Distribution, 12, 2, pp. 388-397, (2018)
  • [17] XIE Min, WANG Tongwen, XU Jingdong, Et al., Effect of distributed generation on relay protection of distribution network and comprehensive improvement of protection scheme, Power System Protection and Control, 47, 19, pp. 78-84, (2019)
  • [18] Measuring relays and protection equipment-part 151: functional requirements for over/under current protection: IEC 60255, (2009)
  • [19] LIU Yujuan, WEI Zhinong, SUN Guoqiang, Et al., Low impedance acceleration inverse-time over-current protection, Power System Technology, 43, 9, pp. 3424-3431, (2019)
  • [20] ELNAILY N, SAAD S M, HUSSEIN T, Et al., A novel constraint and non-standard characteristics for optimal over-current relays coordination to enhance microgrid protection scheme, IET Generation, Transmission & Distribution, 13, 6, pp. 780-793, (2019)