Pilot Protection Based on Cosine Similarity for Transmission Line Connected to Wind Farms

被引:0
|
作者
Jia K. [1 ]
Zheng L. [1 ]
Bi T. [1 ]
Yang Z. [1 ]
Li Y. [2 ]
Han J. [3 ]
机构
[1] State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources (North China Electric Power University), Changping District, Beijing
[2] North China Branch of State Grid Corporation of China, Xicheng District, Beijing
[3] Electrical Power Research Institute of Inner Mongolia, Inner Mongolia Electric Power Co., Ltd., Hohhot, 010020, Inner Mongolia Autonomous Region
来源
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering | 2019年 / 39卷 / 21期
基金
中国国家自然科学基金; 国家重点研发计划;
关键词
Cosine similarity; Pilot protection; Wind farm;
D O I
10.13334/j.0258-8013.pcsee.181540
中图分类号
学科分类号
摘要
The generation principle of the renewable energy power plants, such as wind farms, is different from that of the synchronous machine, which causes the fault characteristics to be different between them. The decline of the traditional protection performance occurs, and even the traditional protections may maloperate or reject operation because of the distinct fault characteristics. In order to solve problems faced by power frequency protection, it was found that there are great differences between transient current waveform characteristics of various wind farms and synchronous machines. When the internal fault occurs in the transmission line, the difference of transient current waveform between both sides is huge, but the difference between the two sides is very small when the external fault occurs because a traversing current flows through the line. Using this difference of waveforms, a principle of pilot protection based on cosine similarity was proposed. The simulation results show that the proposed principle can reliably identify the internal faults and external faults, and it have the ability to withstand the transition resistance and noise. The proposed principle has good performance under the conventional sampling frequency. It is suitable for the existing wind farms. Field data verifies the effectiveness of the proposed protection and it is suitable to realize the industry application. © 2019 Chin. Soc. for Elec. Eng.
引用
收藏
页码:6263 / 6274
页数:11
相关论文
共 37 条
  • [1] Wang C., Song G., Liu K., Et al., Adaptability analysis of fault component protection of power systems with wind farms, Proceedings of the CSEE, 34, 31, pp. 5485-5492, (2014)
  • [2] Li Y., Jia K., Bi T., Et al., Influence mechanism of inverter-interfaced renewable energy generators on fault component based directional relay, Power System Technology, 41, 10, pp. 3230-3236, (2017)
  • [3] Liu S., Bi T., Wang X., Et al., Fault current characteristics of inverter interfaced renewable energy generators with asymmetrical fault ride-through capability, Automation of Electric Power Systems, 40, 3, pp. 66-73, (2016)
  • [4] Liu S., Bi T., Xue A., Et al., Analysis and calculation for short-circuit current characteristics for doubly-fed induction generators with asymmetrical fault-ride-through capability, Transactions of China Electrotechnical Society, 31, 19, pp. 182-190, (2016)
  • [5] Qu J., Wu X., Yan K., Et al., Influence of PV station weak power feature on relay protection of outgoing transmission line, Electric Power Automation Equipment, 35, 5, pp. 146-151, (2015)
  • [6] Li Y., Jia K., Bi T., Et al., Adaptability analysis of current differential protection of outgoing transmission line emanating from inverter-interfaced renewable energy power plants, Automation of Electric Power Systems, 41, 12, pp. 100-105, (2017)
  • [7] Liao Z., He S., Dong X., Et al., Research on the system protection for enhancing the accommodation and transmission of large scale wind power, Power System Protection and Control, 43, 22, pp. 41-46, (2015)
  • [8] Li J., Gao H., Zhu G., Inverse-time current differential protection in active distribution network considering characteristics of Inverter-Interfaced distributed, Transactions of China Electrotechnical Society, 31, 17, pp. 74-83, (2016)
  • [9] He S., Suonan J., Yang C., Et al., A 750kV transmission line pilot protection suitable to Jiuquan wind power base delivery, Power System Protection and Control, 38, 16, pp. 87-91, (2010)
  • [10] Xu S., Lu Y., A pilot protection method for distribution network with distributed generators, Automation of Electric Power Systems, 39, 9, pp. 113-118, (2015)