Passivity-Based Stabilization of a Grid-Connected Three-Phase Inverter System with Feedforward Control

被引:0
作者
Kato T. [1 ]
Inoue K. [1 ]
Yamamoto Y. [1 ]
Yomura K. [1 ]
机构
[1] Department of Electrical Engineering, Doshisha University Kyotanabe, Kyoto
关键词
Digital control; Feedforward control; Grid-connected inverter; Optimal control; Passivity-based control; Stabilization;
D O I
10.1541/ieejeiss.140.1189
中图分类号
学科分类号
摘要
Instabilities due to mutual interactions among inverters and grid systems are sometimes observed. This paper proposes an optimal digital controller design method for passive stabilization of a grid-connected three-phase inverter with LCL filter to improve output frequency impedance characteristics which sufficiently satisfy the Nyquist stability criterion. The principle is that the output impedance can be designed to be passive with the designed feedforward loop characteristics and the system is assured to be stable even if the grid system is weak. The proposed three-phase control consists of the following three steps. In the first step, the state feedback control gains for a single-phase control subsystem are designed to have a good sinusoidal tracking characteristic according to the optimal control. The designed characteristic of the output impedance may not be passive at a certain frequency band. In the second step, a resistive characteristic is added to the band by a new feedforward control design based on a fitting method to make the total characteristic passive and to ensure stability. In the third step, combining two sets of the designed single-phase control subsystems, a three-phase control system is derived. The principle and the design process are described and the designed system is investigated and validated for stability and response characteristics through simulation and experimental results. c 2020 The Institute of Electrical Engineers of Japan.
引用
收藏
页码:1189 / 1197
页数:8
相关论文
共 17 条
[11]  
Harnefors L., Yepes A.G., Vidal A., Douval-Gandoy J., Passivity-based stabilization of resonant current controllers with consideration of Time Delay, IEEE Trans. on Power Electron, 29, 12, pp. 6260-6263, (2014)
[12]  
Kato T., INoue K., Nakajima Y., Yamamoto Y., Design of Passivity-Based Stabilized Control of Grid-Connected Inverter System with LCL Filter, IEEJ Trans. IA, 139, 1, pp. 93-101, (2019)
[13]  
Kato T., Inoue K., Nakajima Y., Stabilization of grid-connected inverter system with feed-forward control, IEEE Energy Conversion Congress and Exposition (ECCE), pp. 3375-3382, (2017)
[14]  
Kato T., Inoue K., Yamamoto Y., Optimal Digital Controller Design for Passive Stabilization of a Grid-Connected Three-Phase Inverter with LCL filter, IEEE Energy Conversion Congress and Exposition (ECCE), pp. 455-461, (2019)
[15]  
Gustavsen B., Semlyen A., Rational approximation of frequency domain responses by vector fitting, IEEE Trans. Power Delivery, 14, 3, pp. 1052-1061, (1999)
[16]  
Kato T., Inoue K., Donomoto Y., Sinusoidal current-tracking control for utility interactive inverter with an LCL Filter, IEEJ Trans. EIS, 131, 11, pp. 1858-1863, (2011)
[17]  
Semasa M., Kato T., Inoue K., Simple and Effective Time Delay Compensation Method for Active Damping Control of Grid-Connected Inverter with an LCL Filter, IEEJ Trans. IA, 7, 6, pp. 454-461, (2018)