SORPTION DEHUMIDIFICATION OF NATURAL-GAS EXHAUST

被引:10
作者
LAZZARIN, RM
LONGO, GA
PICCININNI, F
机构
[1] Istituto di Fisica Tecnica, Politecnico di Bari
来源
HEAT RECOVERY SYSTEMS & CHP | 1992年 / 12卷 / 05期
关键词
D O I
10.1016/0890-4332(92)90059-Q
中图分类号
O414.1 [热力学];
学科分类号
摘要
The calorific value of a natural gas can be fully utilized only if the content of water vapour in exhaust gases is condensed. This can be obtained in condensing boilers. Another possibility is to dry the exhaust before discharge by sorption dehumidification. The sorbent can be regenerated directly by the boiler. The vapour developed in the regenerator can be condensed in a condenser with useful effect. Simulations give an efficiency higher than 97% with respect to the Gross Calorific Value.
引用
收藏
页码:385 / 389
页数:5
相关论文
共 6 条
[1]  
Lazzarin, Schibuola, Performance analysis of heating plants equipped with condensing boiler, Heat Recovery Systems, 6, pp. 269-276, (1986)
[2]  
Lazzarin, Le caldaie a condensazione. Dalla teoria agli impianti, (1986)
[3]  
Treybal, Mass Transfer Operations, (1990)
[4]  
Factor, Grossman, A packed bed dehumidifier/regenerator for solar air conditioning with liquid desiccants, Solar Energy, 24, pp. 541-550, (1980)
[5]  
Gandhidasan, Kettleborough, Rifat Ullah, Calculation of heat mass transfer coefficients in a packed tower operating with a desiccant-air contact system, J. Solar Energy Engng, 108, pp. 123-128, (1986)
[6]  
Gandhidasan, Kettleborough, Rifat Ullah, Analysis of heat and mass transfer between a desiccant-air system in a packed tower, J. Solar Energy Engng, 109, pp. 89-93, (1987)