PERFORMANCE OF METAL-OXIDE ARRESTERS EXPOSED TO FERRORESONANCE IN PADMOUNT TRANSFORMERS

被引:8
作者
WALLING, RA
HARTANA, RK
RECKARD, RM
SAMPAT, MP
BALGIE, TR
机构
[1] GE CO,DISTRIBUT TRANSFORMERS,HICKORY,NC
[2] VIRGINIA POWER,RICHMOND,VA
关键词
METAL-OXIDE ARRESTERS; UNDERGROUND DISTRIBUTION SYSTEMS; FERRORESONANCE; TEMPORARY OVERVOLTAGES;
D O I
10.1109/61.296258
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Ferroresonant overvoltages have been recognized as a threat to arresters installed on underground distribution systems. Extensive tests have been performed to evaluate the thermal and electrical performance of MOV arresters exposed to this duty. Arrester discharge currents were found to be small and arrester heating is slow. The eventual temperature rise and the potential for thermal instability depends greatly on the type of arrester. Arrester designs which promote better beat dissipation to the ambient are shown to reach an acceptable steady-state temperature when exposed to ferroresonance of indefinite duration.
引用
收藏
页码:788 / 795
页数:8
相关论文
共 11 条
[1]  
AUER GG, 1954, AIEE T AUG
[2]   THE APPLICATION OF GAPLESS ARRESTERS ON UNDERGROUND DISTRIBUTION-SYSTEMS [J].
BURKE, JJ ;
SAKSHAUG, EC ;
SMITH, SL .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (03) :1234-1243
[3]  
CRANN LB, 1956, AIEE T 1, V73, P1208
[4]   FERRORESONANT OVERVOLTAGE CONTROL BASED ON TNA TESTS ON 3-PHASE DELTA-WYE TRANSFORMER BANKS [J].
HOPKINSON, RH .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1967, PA86 (10) :1258-+
[5]   APPLYING METAL-OXIDE SURGE ARRESTERS ON DISTRIBUTION-SYSTEMS [J].
KERSHAW, SS ;
GAIBROIS, GL ;
STUMP, KB .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (01) :301-307
[6]  
MILLET RD, 1990, ASSESSMENT MITIGATIO
[7]  
MORK BA, 1993, JUL IEEE SUMM PES M
[8]   METAL-OXIDE ARRESTERS ON DISTRIBUTION-SYSTEMS FUNDAMENTAL CONSIDERATIONS [J].
SAKSHAUG, EC ;
BURKE, JJ ;
KRESGE, JS .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (04) :2076-2089
[9]  
SHORT TA, 1993, JAN IEEE PES WINT M
[10]  
SMITH DR, 1975, IEEE T POWER APPARAT, V94