GRAVITY LOAD EFFECT ON SEISMIC BEHAVIOR OF INTERIOR SLAB-COLUMN CONNECTIONS

被引:0
作者
ROBERTSON, IN
DURRANI, AJ
机构
[1] Walter P. Moore and Associates, Houston, United States
关键词
COLUMNS (SUPPORTS); CONNECTIONS; CYCLIC LOADS; DUCTILITY; FLAT CONCRETE PLATES; FLAT CONCRETE SLABS; PUNCHING SHEAR; REINFORCED CONCRETE; STIFFNESS; STRENGTH;
D O I
暂无
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The effect of superimposed slab loading on the behavior of interior slab-column connections was studied by testing two-bay slab-column subassemblies. Each subassembly consisted of one interior and two exterior connections. Three identical slab-column subassemblies were subjected to the same cyclic lateral displacement routine while each supported a different superimposed slab load. The tests show that increased slab load substantially reduces both the unbalanced moment capacity and the lateral drift capacity of the connections. A limiting shear stress is suggested to insure adequate drift capacity for interior slab-column connections. The test results are compared with present ACI 318-83 Building Code provisions and ACI Committee 352 recommendations for design of slab-column connections.
引用
收藏
页码:37 / 45
页数:9