ANALYSIS OF SWITCHING TRANSIENTS OF A DEENERGIZED CIRCUIT IN A DOUBLE-CIRCUIT TRANSMISSION-LINE

被引:0
作者
YANG, CS
MATSUURA, K
机构
[1] Faculty of Engineering, Osaka University, Suita, Osaka
关键词
D O I
10.1016/0378-7796(90)90030-7
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Determination of the capacity of the earthing switch for the de-energized line used in a substation requires a precise analysis of the transient induction voltage and current during a switching operation caused by the nearby live line. This paper shows that the line conductor height has the strongest effect on the steady-state induced voltage of the de-energized line of a double-circuit transmission line, and that geometrical factors should be taken into consideration carefully for long distance lines installed in mountainous areas. As for the transient current and voltage following the switching operation, the analytical results show that the timing of the switching operation is a key factor determining the maximum transient current experienced by the earthing switches and the maximum transient voltage attained is twice the steady-state induced voltage. The inclusion of line parameter frequency dependence decreases the crest value of the transient voltage and decreases its attenuation time constant. © 1990.
引用
收藏
页码:177 / 185
页数:9
相关论文
共 7 条
[1]  
Perz, Raghuveer, Transmission line—effect of earth resistivity on magnetic field, images and equivalent circuit, IEEE Trans., 95 PAS, pp. 2135-2143, (1979)
[2]  
Gary, Moreau, Predetermination of the interference level for high voltage transmission lines, I. Field calculations method, IEEE Trans., 91 PAS, pp. 292-300, (1972)
[3]  
Yang, Matsuura, Tree shielding effect on the induced voltage in a de-energized line of a double-circuit transmission line, Kansai Branch Joint Convention Record, (1986)
[4]  
Yang, Matsuura, Effect of conductor height and terrain on the steady-state induced voltage and transient current through a linesman's body on a de-energized line, Electr. Power Syst. Res., 15, pp. 219-227, (1988)
[5]  
Balasubramanian, Gupta, Calculation of transient due to fault initiation on a double-circuit transmission line, Proc. Inst. Electr. Eng., 123, pp. 537-542, (1976)
[6]  
Galloway, Shorrocks, Wedepohl, Calculation of electrical parameters for short and long polyphase transmission lines, Proceedings of the Institution of Electrical Engineers, 11, pp. 2051-2059, (1964)
[7]  
Carson, Wave propagation in overhead wires with ground return, Bell System Technical Journal, 5, pp. 539-554, (1926)