Calculation of indirect-lightning flashover rate on distribution lines from indirect lightning in tropical zones

被引:0
|
作者
Soto-Rios, Edison [1 ]
Perez-Gonzalez, Ernesto [2 ]
del Rio-Trujillo, Diego [3 ]
机构
[1] Univ Ind Santander, Escuela Ingn Elect Elect & Telecomunicac, Grp Invest Sistemas Energia Elect GISEL, Bucaramanga, Colombia
[2] Univ Nacl Colombia, Dept Energia Elect & Automat, Programa Invest Adquisic & Anal Senales PAAS, Medellin, Colombia
[3] Univ Nacl Colombia, Dept Ingn Elect Elect & Comp, Manizales, Colombia
来源
UIS INGENIERIAS | 2018年 / 17卷 / 01期
关键词
Lightning parameters; flashover rate; distribution lines; lightning induced voltages; CIGRE; MCS;
D O I
10.18273/revuin.v17n1-2018021
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In this paper the indirect-lightning flashover rate of a distribution line is obtained following the procedure described in the IEEE Std. 1410 - 2010, but using other parameters of the first stroke distributions (peak current and front time) adopted by CIGRE. These parameters were taken from the measured currents of the Morro do Cachimbo Station in Belo Horizonte - Brazil, which are representative of the tropical zone. As a result, the calculated flashover rate with the data of tropical zone is higher than one obtained with the CIGRE curves. Such increments could be in the most extreme case of 70%.
引用
收藏
页码:217 / 222
页数:6
相关论文
共 50 条
  • [1] Indirect-lightning performance of distribution lines: Influence of protection devices
    Borghetti, A.
    Nucci, C. A.
    Paolone, M.
    Rachidi, F.
    2005/2006 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, 2006, : 455 - +
  • [2] Calculation of Lightning Flashover Rates of Overhead Distribution Lines Considering Direct and Indirect Strokes
    Chen, Jiming
    Zhu, Mingxiao
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2014, 56 (03) : 668 - 674
  • [3] Indirect-Lightning Performance of Overhead Distribution Networks With Complex Topology
    Borghetti, Alberto
    Nucci, Carlo Alberto
    Paolone, Mario
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) : 2206 - 2213
  • [4] Influence of a shield wire flashover on the indirect lightning performance assessment of distribution lines
    Yamanaka, Akifumi
    Ishimoto, Kazuyuki
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 223
  • [5] Flashover Rate of Distribution Line Due to Indirect Negative Lightning Return Strokes
    Michishita, Koji
    Ishii, Masaru
    Hongo, Yasuji
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) : 472 - 479
  • [6] Flashover rate due lightning in overhead distribution lines
    Vasquez, Carmen
    Osal, William
    Blanco, Carolina
    PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON ELECTRICAL POWER QUALITY AND UTILISATION, VOLS 1 AND 2, 2007, : 834 - 837
  • [7] Lightning characterization for flashover rate calculation of overhead transmission lines
    Martinez, Juan A.
    Castro-Aranda, Ferley
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 674 - +
  • [8] Lightning Performance of Distribution Lines due to Positive and Negative Indirect Lightning Flashes
    Napolitano, F.
    Tossani, F.
    Borghetti, A.
    Nucci, C. A.
    Rachidi, F.
    2017 1ST IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2017 17TH IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC / I&CPS EUROPE), 2017,
  • [9] Calculation of lightning flashover rates of overhead distribution lines. A comparative study
    Martinez, JA
    Gonzalez-Molina, F
    Chowdhuri, P
    2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4, 2000, : 2577 - 2582
  • [10] Indirect lightning performance of 10-kV overhead distribution lines
    Yu, Jianli
    Gu, Shanmao
    Liu, Jianjun
    Liu, He
    FRONTIERS IN ENERGY RESEARCH, 2024, 12