Aspects of surge arresters' maximum operating voltage choice for electrical equipment insulation protection in 6...35 kV mains

被引:0
|
作者
Shumilov, Yu. N. [1 ,2 ]
机构
[1] State Enterprise Sci Res Inst High Voltage, Tech Sci, 22 Gen Batyuka St, UA-84100 Slavyansk, Donetsk Region, Ukraine
[2] State Enterprise Sci Res Inst High Voltage, 22 Gen Batyuka St, UA-84100 Slavyansk, Donetsk Region, Ukraine
关键词
non-linear surge arrester; insulation; arc fault;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper shows that, in 6.35 kV mains, application of a non- linear surge arrester (SA) with the maximum continuous admissible operating voltage which is 10% higher than the mains' maximum operating voltage results in the SA protection from overheating and subsequent breakdown at nonnormable lifetime of single-phase arc faults.
引用
收藏
页码:69 / 71
页数:3
相关论文
共 5 条