INCORPORATION OF HVDC AND SVC MODELS IN THE NORTHERN-STATE-POWER-CO (NSP) NETWORK FOR ONLINE IMPLEMENTATION OF DIRECT TRANSIENT STABILITY ASSESSMENT

被引:14
作者
JING, C [1 ]
VITTAL, V [1 ]
EJEBE, GC [1 ]
IRISARRI, GD [1 ]
机构
[1] EMPROS SYST INT,PLYMOUTH,MN 55441
关键词
HVDC; SVC; TRANSIENT ENERGY FUNCTION; TRANSIENT STABILITY;
D O I
10.1109/59.387931
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper we discuss the incorporation of the 4 de systems and 2 SVCs in the NSP network for on-line implementation of direct transient stability assessment. The de and SVC models used are more complicated than those used in the existing AC-DC-SVC Transient Energy Function (TEF) literature. In this new approach, the commutation failure of the HVDC is also considered. It is necessary to use these complicated de and SVC models because in the NSP network they are located in an area where the transient stability is of great concern. The de and SVC systems are treated as part of the ac network and their effect on the transient energy function is included. The effect of de and SVC on the calculation of the potential energy is reflected in the ac network solution. The equivalent models and the proposed procedure developed is tested on a NSP equivalent network of 273 generators and 2217 buses. The result obtained are in excellent agreement with those obtained by time domain simulation using EPRI ETMSP V3.0.
引用
收藏
页码:898 / 904
页数:7
相关论文
共 18 条
[1]  
Arrillaga J., 1990, COMPUTER ANAL POWER
[2]  
CHIANG HD, 1991, IEEE SPM91 PAP
[3]  
DEMARCO CL, 1991 IEEE PES SUMM M
[4]  
EJEBE GC, 1993, EPRI RP31033 FIN REP
[5]  
Fouad A. A., 1992, POWER SYSTEM TRANSIE
[6]  
HILL DJ, 1990, 11TH P IFAC WORLD C, V12, P19
[7]   INCORPORATION OF SVCS INTO ENERGY FUNCTION METHODS [J].
HISKENS, IA ;
HILL, DJ .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :133-140
[8]   ENERGY FUNCTIONS, TRANSIENT STABILITY AND VOLTAGE BEHAVIOR IN POWER-SYSTEMS WITH NONLINEAR LOADS [J].
HISKENS, IA ;
HILL, DJ .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1989, 4 (04) :1525-1533
[9]  
IRISARRI GD, 1993, 1993 POWER INDUSTRY COMPUTER APPLICATION CONFERENCE : CONFERENCE PROCEEDINGS, P426
[10]   A SIMPLIFIED 2-TERMINAL HVDC MODEL AND ITS USE IN DIRECT TRANSIENT STABILITY ASSESSMENT [J].
NI, YX ;
FOUAD, AA .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1987, 2 (04) :1006-1012