DESIGN STUDIES FOR THE MEAD-PHOENIX 500 KV AC TRANSMISSION PROJECT

被引:7
作者
THALLAM, RS
LUNDQUIST, TG
ATMURI, SR
SELIN, DA
机构
[1] TESHMONT CONSULTANTS INC,WINNIPEG,MB,CANADA
[2] ARIZONA PUBL SERV CO,PHOENIX,AZ
关键词
SERIES COMPENSATION; PHASE SHIFTING TRANSFORMER; LINE ENERGIZATION; BREAKER TRV; REACTOR SWITCHING;
D O I
10.1109/61.473369
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The Mead-Phoenix 500 kV ac line is 243 miles long and runs parallel to the existing Mead-Liberty 345 kV line. This line is planned for 70% series and 70% shunt compensation; it also incorporates the first application of a 500 kV phase shifting transformer that enables a 1300 MW transmission capacity. This paper presents the design studies that were undertaken in arriving at the equipment ratings and insulation levels that lead to the equipment specifications. The shunt reactor switching requirements utilizing MOV across the breaker,line switching with line connected arresters and the breaker transient recovery voltage are also dealt with in the paper.
引用
收藏
页码:1862 / 1874
页数:13
相关论文
共 15 条
[11]  
MUSIL RJ, 1982, IEEE T PAS, V101
[12]  
RECKLEFF JG, 1988, CIGRE1316 PAP
[13]  
RIBEIRO JR, 1989, IEEE T, V4
[14]  
1984, 1214 PAP
[15]  
EMTP REVISED APPLICA