IN-SERVICE PARTIAL DISCHARGE TESTING OF GENERATOR INSULATION

被引:5
作者
KURTZ, M
STONE, GC
机构
[1] Ontario Hydro, Research Division, Toronto
来源
IEEE TRANSACTIONS ON ELECTRICAL INSULATION | 1979年 / 14卷 / 02期
关键词
D O I
10.1109/TEI.1979.298161
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Progressive degradation of high-voltage generator insulation, whether due directly to the erosive effects of internal or slot discharge or to other debilitating factors such as heat and vibration, may be detected and monitored as a function of time by in-situ partial-discharge tests. This paper describes new diagnostic test techniques for assessing the condition of generator insulation with a minimum of service interruption. An improved means of coupling or data acquisition is described, as well as a versatile single-channel pulse height analyzer with characteristics adequate for a field application of this type. Some typical test data are given. These studies were sponsored by the Canadian Electrical Association and are presented with their permission. Copyright © 1979 by The Institute of Electrical and Electronics Engineers, Inc.