Modeling of Finned-Tube Heat Exchanger Using in Air Conditioning System

被引:0
作者
Khotphan, Suphod
机构
来源
SURANAREE JOURNAL OF SCIENCE AND TECHNOLOGY | 2006年 / 13卷 / 01期
关键词
Air conditioning; finned-tube heat exchange; three zone; R-134a;
D O I
暂无
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
This paper proposes mathematical models of evaporator and condenser used in a domestic air conditioning system with wavy fin and the refrigerant R-134a is used as a working fluid. By using the simulation method, the model for the evaporator with condensation of the water vapor on the outer surface is divided into three parts: dry two-phase (DTP), wet two-phase (WTP) and superheated (SH). The model for the condenser with dry surface is also divided into three parts: de-superheating (DSH), condensing (COND) and sub-cooling (SC). Hence each section must be modeled separately and coded into a computer visual basic program for evaluating the exit temperature of heat exchanges, heat transfer rate and parameters of prime importance to design heat exchanges for air conditioning system.
引用
收藏
页码:20 / 28
页数:9
相关论文
共 6 条
  • [1] Dittus F.W., 1930, HEAT TRANSFER AUTOMO, V2, P443
  • [2] McQuiston F. C., 1977, HEATING VENTILATING, P547
  • [3] Shah M.M., 1982, ASHRAE T, V88, P185
  • [4] Modeling cooling coils
    Theerakulpisut, S
    Priprem, S
    [J]. INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 1998, 25 (01) : 127 - 137
  • [5] Threlkeld J. L, 1970, THERMAL ENV ENG, P254
  • [6] WEBB RL, 1990, ASHRAE TRAN, V96, P445