POWER SYSTEM TESTING AND ANALYSIS;
POWER SYSTEM MONITORING;
DYNAMIC PERFORMANCE;
CONTROL DESIGN;
MODAL ANALYSIS;
D O I:
10.1109/61.252613
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
As a part of an EPRI-sponsored development on advanced power modulation control system for HVDC lines, dynamic system monitors (DSM) were installed at the dc terminals of the Square Butte system. The monitors were used to validate the computer models used for the controller design and will be used to validate the performance of the controllers after installation. The paper describes the use of Prony analysis and Fourier techniques to analyze system disturbances and to validate the computer models. As described in the paper, excellent results have been achieved at least for parts of the system for some well defined disturbances.