STANDARDIZED SENSITIVITY COEFFICIENTS FOR POWER-SYSTEM NETWORKS

被引:17
作者
BARCELO, WR
LEMMON, WW
机构
[1] MSU System Services Inc, New, Orleans, LA, USA
关键词
Mathematical Techniques--Sensitivity Analysis - Mathematical Transformations;
D O I
10.1109/59.192969
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A simple mathematical transformation for converting power-system network sensitivity coefficients from one reference frame to another is derived using a generalized power center concept. The generalized power center consists of a swing power center and an angle center. A standard power center is presented wherein the swing power and angle centers are set equal to the load center. The resulting standardized sensitivity coefficients are independent of the swing bus. Solving a Lagrangian formulation of the economic dispatch problem results in the direct calculation of true system incremental cost only when standardized sensitivity coefficients are used. Results are presented for several practical cases involving the Jacobian and DC load-flow matrices and several different power centers.
引用
收藏
页码:1591 / 1599
页数:9
相关论文
共 6 条
  • [1] Kirchmayer L. K., 1958, EC OPERATION POWER S
  • [2] IMPROVED LOSS FORMULA COMPUTATION BY OPTIMALLY ORDERED ELIMINATION TECHNIQUES
    MEYER, WC
    ALBERTSON, VD
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (01): : 62 - +
  • [3] SANDERS CW, 1987, WIN IEEE POW M NEW O
  • [4] FAST DECOUPLED LOAD FLOW
    STOTT, B
    ALSAC, O
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1974, PA93 (03): : 859 - 869
  • [5] REAL-TIME OPTIMIZER FOR SECURITY DISPATCH
    WOLLENBERG, BF
    STADLIN, WO
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1974, PA93 (05): : 1640 - 1649
  • [6] Wood AJ, 1984, POWER GENERATION OPE