Experimental investigation on the flow behaviour in a bubble pump of diffusion absorption refrigeration systems

被引:12
作者
Benhmidene, Ali [1 ]
Hidouri, Khaoula [1 ]
Chaouachi, Bechir [1 ]
Gabsi, Slimane [1 ]
Bourouis, Mahmoud [2 ]
机构
[1] Ecole Natl Ingenieurs Gabes, URECAP, Route Med, Zrig Eddakhlania, Tunisia
[2] Univ Rovira & Virgili, Dept Mech Engn, Av Paisos Catalans 26, E-43007 Tarragona, Spain
关键词
Diffusion absorption refrigeration; Bubble pump; Flow pattern; Oscillation flow;
D O I
10.1016/j.csite.2016.04.002
中图分类号
O414.1 [热力学];
学科分类号
摘要
An experimental investigation on the performance of a bubble pump for diffusion absorption refrigeration (DAR) systems was carried-out. The characteristics and operating conditions of the bubble pump determine the efficiency of the DAR systems. An experimental set-up operating in continuous mode was designed, built-up and successfully operated as a bubble pump. Experiments were performed by changing some of the parameters affecting the bubble pump performance. The experimental results showed that the performance of the bubble pump was mainly dependent on the driving heat input and the submersion ratio. Driving heat inputs applied were between 20 W and 200 W for a suitable size of the pump tubes. Three submersion ratios were tested, namely 25%, 35% and 45%. The results obtained showed that an oscillating flow was present in the operation of the bubble pump and the frequency of oscillation increased with the increase of the submersion ratio. The average mass flow rate of the refrigerant (ammonia) pumped increased with increase in the heating power; however, mass flow rates of the poor and rich solutions were function of the flow regime. In addition, experimental results were used to determine the optimal heating power for the different submersion ratios considered in this study. The optimal heating power ranged from 30 W to 130 W for a submersion ratio of 25% and from 30 W to 80 W for the submersion ratios of 35% and 45%. (C) 2016 Published by Elsevier Ltd.
引用
收藏
页码:1 / 9
页数:9
相关论文
共 18 条
  • [1] Experimental studies on bubble pump operated diffusion absorption machine based on light hydrocarbons for solar cooling
    Ben Ezzine, N.
    Garma, R.
    Bourouis, M.
    Bellagi, A.
    [J]. RENEWABLE ENERGY, 2010, 35 (02) : 464 - 470
  • [2] A review of bubble pump technologies
    Benhmidene A.
    Chaouachi B.
    Gabsi S.
    [J]. Journal of Applied Sciences, 2010, 10 (16) : 1806 - 1813
  • [3] Benhmidene A., 2011, ASM J FLUIDS ENG, V133
  • [4] Modeling of Boiling Two-Phase Flow in the Bubble Pump of Diffusion-Absorption Refrigeration Cycles
    Benhmidene, Ali
    Chaouachi, Bechir
    Gabsi, Slimane
    Bourouis, Mahmoud
    [J]. CHEMICAL ENGINEERING COMMUNICATIONS, 2015, 202 (01) : 15 - 24
  • [5] EFFECT OF OPERATING CONDITIONS ON THE PERFORMANCE OF THE BUBBLE PUMP OF ABSORPTION-DIFFUSION REFRIGERATION CYCLES
    Benhmidene, Ali
    Chaouachi, Bechir
    Bourouis, Mahmoud
    Gabsi, Slimane
    [J]. THERMAL SCIENCE, 2011, 15 (03): : 793 - 806
  • [6] Modelling of heat flux received by a bubble pump of absorption-diffusion refrigeration cycles
    Benhmidene, Ali
    Chaouachi, Bechir
    Gabsi, Slimane
    Bourouis, Mahmoud
    [J]. HEAT AND MASS TRANSFER, 2011, 47 (11) : 1341 - 1347
  • [7] Delano A., 1998, THESIS
  • [8] Numerical investigations of the heating distribution effect on the boiling flow in bubble pumps
    Garma, Raoudha
    Stiriba, Youssef
    Bourouis, Mahmoud
    Bellagi, Ahmed
    [J]. INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2014, 39 (27) : 15256 - 15260
  • [9] Simulation and experimental investigation into diffusion absorption cooling machines for air-conditioning applications
    Jakob, U.
    Eicker, U.
    Schneider, D.
    Taki, A. H.
    Cook, M. J.
    [J]. APPLIED THERMAL ENGINEERING, 2008, 28 (10) : 1138 - 1150
  • [10] Pumping characteristics of a thermosyphon applied for absorption refrigerators with working pair of LiBr/water
    Jeong, S
    Lee, SK
    Koo, KK
    [J]. APPLIED THERMAL ENGINEERING, 1998, 18 (12) : 1309 - 1323