TRANSIENT AC VOLTAGE RELATED PHENOMENA FOR HVDC SCHEMES CONNECTED TO WEAK AC SYSTEMS

被引:27
作者
PILOTTO, LAS
SZECHTMAN, M
HAMMAD, AE
ANDERSSON, G
LISS, G
机构
[1] ABB POWER SYST AB,LUDVIKA,SWEDEN
[2] ABB ASEA BROWN BOVERI,CH-5401 BADEN,SWITZERLAND
关键词
VOLTAGE STABILITY; HVDC CONVERTER CONTROLS; DIGITAL SIMULATION;
D O I
10.1109/61.141857
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A didactic explanation of voltage stability associated phenomena at HVDC terminals is presented. Conditions leading to ac voltage collapse problems are identified. A mechanism that excites control-induced voltage oscillations is shown. The voltage stability factor is used for obtaining the maximum power limits of ac/dc systems operating with different control strategies. Correlation to Pd x Id curves is given. Solutions for eliminating the risks of voltage collapse and for avoiding control-induced oscillations are discussed. The results are supported by detailed digital simulations of a weak ac/dc system using EMTP.
引用
收藏
页码:1396 / 1404
页数:9
相关论文
共 16 条
[1]   POWER SYSTEM VOLTAGE STABILITY [J].
ABE, S ;
FUKUNAGA, Y ;
ISONO, A ;
KONDO, B .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (10) :3830-3840
[2]  
AINSWORTH JD, 1985, SEP CIGRE C HVDC WEA
[3]  
Barbier C, 1980, REV GEN ELECTR, P3
[4]  
CONCORDIA C, 1987 IEEE PES SUMM M
[5]   ANALYSIS OF HVDC CONVERTERS CONNECTED TO WEAK AC SYSTEMS [J].
FRANKEN, B ;
ANDERSSON, G .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (01) :235-242
[6]  
GAVRILOVIC A, 1987, CIGRE S AC DC TRANSM
[7]  
HAMMAD A, 1984, JUN INT C DC POW TRA, P164
[8]  
HAMMAD AE, 1990, WIN IEEE PES M ATL
[9]  
HAMMAD AE, 1988, IEEE T PWRS, V1, P209
[10]  
KUNDUR P, 1987 IEEE PES SUMM M