APPLICATION OF ADVANCED AFTER-LAYING TEST TO LONG-DISTANCE 275-KV XLPE CABLE LINES

被引:14
|
作者
OTA, H
ICHIHARA, M
MIYAMOTO, N
KITAI, S
MARUYAMA, Y
FUKASAWA, M
TAKEHANA, H
机构
[1] SUMITOMO ELECT IND LTD,OSAKA,JAPAN
[2] FURUKAWA ELECT CORP LTD,CHIBA,JAPAN
[3] HITACHI CABLE LTD,HITACHI,IBARAKI,JAPAN
[4] FUJIKURA LTD,TOKYO 135,JAPAN
关键词
D O I
10.1109/61.400876
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Long-distance XLPE cable lines were laid over a distance of 26.9 km (South Route) using the newly established 275 kV XLPE cable technology and in-situ jointing technique. Field ac HV withstanding testing was conducted on these lines as the after-laying test - the first such test for long-distance EHV XLPE cable lines. For this test, small resonance type ac withstanding HV test equipment was developed. A new system was also established for direct and simultaneous measurement of partial discharge over the entire cable length. One latent defect was detected in this test, proving that the test method is extremely effective in confirming the quality of XLPE cable lines.
引用
收藏
页码:567 / 579
页数:13
相关论文
共 18 条
  • [1] Results on after-laying test of 275kV XLPE cable line
    Kobayashi, S
    Kawabe, T
    Morimoto, N
    Shinoda, A
    Shimohiro, D
    Kawai, T
    PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2003, : 1202 - 1205
  • [2] New after-laying test methods for XLPE cable lines
    Uchida, K
    Kobayashi, S
    Kawashima, T
    Hirotsu, K
    Inoue, H
    Tanaka, H
    Sakuma, S
    ELECTRICAL ENGINEERING IN JAPAN, 1996, 117 (06) : 18 - 30
  • [3] New after-laying test methods for XLPE cable lines
    Uchida, Katsuki
    Kobayashi, Shin'ichi
    Kawashima, Takao
    Hirotsu, Ken'ichi
    Inoue, Hitoshi
    Tanaka, Hideo
    Sakuma, Susumu
    Electrical Engineering in Japan (English translation of Denki Gakkai Ronbunshi), 1996, 117 (06): : 18 - 30
  • [4] Study on an after-laying test for a long-distance GIL
    Nojima, T
    Shimizu, M
    Miyazaki, A
    IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (03) : 718 - 727
  • [5] FIELD-TEST OF 275-KV INTERNALLY WATER COOLED XLPE CABLE SYSTEM
    OGAWA, K
    KURATA, M
    SUZUKI, H
    KAWASAKI, K
    IMAI, N
    NAKAMURA, S
    SAKAI, S
    IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (01) : 8 - 18
  • [6] Long-distance 275-kV GIL monitoring system using fiber-optic technology
    Miyazaki, A
    Takinami, N
    Kobayashi, S
    Nishima, H
    Nakura, Y
    Komeda, H
    Nagano, H
    Higashi, H
    IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (04) : 1545 - 1553
  • [7] The world's first long-distance 500kV-XLPE cable line, part 2: Joints and after-installation test
    Ohki, Y
    Yasufuku, S
    IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (03) : 57 - 58
  • [8] Commissioning Test Methods for Large Capacity and Long-distance AC XLPE Power Cable
    Xiong J.
    Zhang Q.
    Ma G.
    Wang Y.
    Wang W.
    Li C.
    Xiong, Jun (xiongj@guangzhou.csg.cn), 2018, Science Press (44): : 3727 - 3735
  • [9] The world's first long-distance 500-kV XLPE cable line, Part 1: Cable and cable installation
    Ohki, Y
    Yasufuku, S
    IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (02) : 65 - 66
  • [10] Line constant measurements and loading current test in long-distance 275 kV GIL
    Miyazaki, A
    Takinami, N
    Kobayashi, S
    Yamauchi, T
    Hama, H
    Araki, T
    Nishima, H
    Hata, H
    Yamaguchi, H
    IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (02) : 165 - 170